What it means
F07515 is raised when a drive data set assigns a power unit to a motor although this assignment is not connected in the target topology: a power unit (via PDS) has been paired with a motor (via MDS) in a drive data set that the target topology does not connect. The drive also raises the fault when no motor has been assigned to the power unit at all (p0131). The fault value tells you which drive data set is affected.
Why it appears
- A drive data set pairs a power unit (assigned via PDS) with a motor (assigned via MDS), but this drive data set is not connected in the target topology.
- It is possible that a motor has not been assigned to the power unit at all (p0131).
What to check
- Assign the drive data set to a combination of motor and power unit that the target topology permits.
- Alternatively, adapt the target topology.
- If required, for a missing motor, recreate the component (drive Wizard).
Reading the message value
- The message value %1 carries the fault value.
- Fault value in r0949, interpret decimal: number of the incorrectly parameterized drive data set.
Parameters the manual names
- r0949 (fault value) — read it as a decimal number; it contains the number of the incorrectly parameterized drive data set.
- p0131 (motor component number) — check here whether a motor has been assigned to the power unit; a missing assignment triggers this fault.
- p0186 (Motor Data Sets (MDS) number) — identifies the motor data set side of the assignment that has to be corrected.
- p0121 (power unit component number) — identifies the power unit side of the assignment that has to be corrected.
Acknowledging and restarting
The drive coasts down when this fault is raised. Once the drive data set has been assigned to a combination of motor and power unit that the target topology permits (or the target topology has been adapted), acknowledge the fault immediately; the drive only starts again after acknowledgment. If the assignment still does not match the target topology, the fault reappears.
The same on every family
Every manual that describes F07515 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2837 |
| G130, G150 | OFF2 | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1573 |
The drives this code lives on
F07515 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07515 mean in SINAMICS?
A drive data set assigns a power unit to a motor although this combination is not connected in the target topology — or no motor has been assigned to the power unit (p0131).
How do I find the drive data set that triggers F07515?
Read the fault value in r0949 and interpret it as a decimal number; it contains the number of the incorrectly parameterized drive data set.
How is fault F07515 cleared?
Assign the drive data set to a combination of motor and power unit permitted by the target topology, or adapt the target topology. If a motor is missing, recreate the component with the drive Wizard, then acknowledge the fault immediately.
Which parameters belong to fault F07515?
p0131 (motor component number), p0121 (power unit component number) and p0186 (Motor Data Sets (MDS) number); the fault value in r0949 names the affected drive data set.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals