Fault · SINAMICS G130, G150, S120, S150

F07451LR: Position monitoring has responded

What it means

When the drive reports LR: Position monitoring has responded, a positioning move has failed its arrival check: the position monitoring time (p2545) expired before the drive had reached the positioning window (p2544). The LR position monitoring therefore responds. Depending on how the drive is configured, the same condition can also be issued as an alarm (A) instead of a fault.

Why it appears

  • The positioning window (p2544) is parameterized too small.
  • The position monitoring time (p2545) is parameterized too short.
  • The position loop gain (p2538) is too low.
  • The position loop gain (p2538) is too high — the position control then becomes unstable and oscillates (p2538).
  • The drive is mechanically locked.

What to check

  1. Check the mechanics first: the drive must not be mechanically locked.
  2. Check the positioning window (p2544); if it is parameterized too small, increase it.
  3. Check the position monitoring time (p2545); if it is parameterized too short, extend it.
  4. Check the position loop gain (p2538): increase it if it is too low, reduce it if it is too high and the drive oscillates.
  5. Repeat the move and confirm that the drive now reaches the positioning window (p2544) within the position monitoring time (p2545).

Parameters the manual names

  • p2544 (LR positioning window / Pos_window) — the tolerated position window the drive must reach before the monitoring time expires; enlarge it here if it was parameterized too small for this code.
  • p2545 (LR positioning monitoring time / t_pos_mon) — the time the drive is given to enter the positioning window; extend it here if it was parameterized too short for this code.
  • p2538 (LR proportional gain / Kp) — the position loop gain; set it higher if it is too low, and lower if it is too high and causes instability/oscillation.

Acknowledging and restarting

Resolve the cause first. The fault is then acknowledged immediately on the operator panel or in the commissioning tool, and only after acknowledgment does the drive accept a new start; while the condition is active, the drive is brought to a standstill. If the drive signals the same condition as an alarm instead, no reaction and no acknowledgment are required — the alarm clears once the condition no longer applies.

The same on every family

Every manual that describes F07451 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF1 (OFF2, OFF3)IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2819
G130, G150OFF1 (OFF2, OFF3)IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1556

The drives this code lives on

F07451 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07451 mean on a SINAMICS drive?

It reports that the LR position monitoring has responded: the position monitoring time (p2545) expired before the drive had reached the positioning window (p2544) during a positioning move.

What are typical causes of F07451?

The positioning window (p2544) is too small, the position monitoring time (p2545) too short, or the position loop gain (p2538) is too low or so high that the drive oscillates. The drive can also be mechanically locked.

How do I clear and acknowledge F07451?

Resolve one of the causes — enlarge p2544, extend p2545, correct p2538 or free the mechanics — and then acknowledge the fault immediately. When the condition appears only as an alarm, no acknowledgment is needed.

Which parameters belong to fault F07451?

p2544 (LR positioning window), p2545 (LR positioning monitoring time) and p2538 (LR proportional gain).

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals