What it means
The manuals title this message LR: Standstill monitoring has responded
. The LR standstill monitoring expects the drive to stay inside the standstill window (p2542) for the whole of the standstill monitoring time (p2543); if the drive has left the window when that time expires, the drive raises F07450. The fault carries no message value. Depending on how the drive is configured, the same condition can also be output as an alarm (A); in that form it triggers no reaction and requires no acknowledgement.
Why it appears
- The position actual value inversion is set incorrectly (p0410).
- The standstill window is set too small (p2542).
- The standstill monitoring time is set too low (p2543).
- The position loop gain is too low (p2538).
- The position loop gain is too high, so the drive becomes unstable and oscillates (p2538).
- The drive is mechanically overloaded.
- The connecting cable between the motor and the drive converter is incorrect — a phase is missing or interchanged.
- Tracking mode is not selected although motor identification is selected; it must be set with BI: p2655[0] = 1 signal.
- Tracking mode is not selected although the function generator is selected (BI: p2655[0] = 1 signal), or position control is not deactivated (BI: p2550 = 0 signal).
What to check
The manual's remedy reads Check the causes and resolve
. A practical order:
- Check the setting of the position actual value inversion (p0410).
- Check whether the standstill window (p2542) is too small and enlarge it if required.
- Check whether the standstill monitoring time (p2543) is too low and increase it if required.
- Check the position loop gain (p2538) in both directions: a gain that is too low and a gain that is too high (instability/oscillation) can both trigger the fault.
- Check the mechanical system for overload.
- Check the connecting cable between the motor and the drive converter for a missing or interchanged phase.
- If motor identification is selected, select tracking mode (BI: p2655[0] = 1 signal).
- If the function generator is selected, select tracking mode (BI: p2655[0] = 1 signal) and deactivate position control (BI: p2550 = 0 signal).
Parameters the manual names
- p2543 (LR standstill monitoring time): check whether it is set too low.
- p2542 (LR standstill window): check whether it is set too small.
- p0410 (encoder inversion actual value): check whether the position actual value inversion is set correctly.
- p2538 (LR proportional gain): check whether the position loop gain is too low or too high (instability/oscillation).
- p2655 (BI: EPOS select tracking mode): must carry the 1 signal when motor identification is selected.
- p2550 (BI: LR enable 2): must carry the 0 signal to deactivate position control when the function generator is selected.
Acknowledging and restarting
Once the causes have been checked and resolved, the fault can be acknowledged immediately, and the drive is then started again. The fault response stops the drive along the OFF1 response (OFF2 and OFF3 can be set as alternatives). When the condition is output as an alarm (A), no acknowledgement is required.
What differs between the drive families
Straight from the manuals' own fields — F07450 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF1 (OFF2, OFF3) | — | Application/technological function faulted (17) | None | SINAMICS S120, S150 List Manual · p. 2818 |
| G130, G150 | OFF1 (OFF2, OFF3) | IMMEDIATELY | Application/technological function faulted (17) | None | SINAMICS G130, G150 List Manual · p. 1555 |
The drives this code lives on
F07450 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS fault F07450 mean?
It means the LR standstill monitoring has responded: after the standstill monitoring time (p2543) expired, the drive left the standstill window (p2542). The same condition can also be output as an alarm (A).
How do I fix SINAMICS F07450?
Check the causes and resolve them: the standstill window (p2542) may be too small, the monitoring time (p2543) too low, the position loop gain (p2538) too low or too high, the drive mechanically overloaded, or a phase in the motor/converter connecting cable missing or interchanged. After resolving the cause, acknowledge the fault immediately and restart.
Why does F07450 appear when I run motor identification or use the function generator?
Both actions require tracking mode to be selected (BI: p2655[0] = 1 signal), and when the function generator is selected, position control must additionally be deactivated (BI: p2550 = 0 signal). Otherwise the standstill monitoring can respond.
Which parameters are relevant for F07450?
p2543 (LR standstill monitoring time), p2542 (LR standstill window), p0410 (encoder inversion actual value), p2538 (LR proportional gain), p2655 (BI: EPOS select tracking mode) and p2550 (BI: LR enable 2).