Fault · SINAMICS G130, G150, S120, S150

F07458EPOS: Reference cam not found

What it means

F07458 comes from the EPOS search for reference: after the search was started, the axis moved through the maximum permissible distance allowed for the search without actually finding the reference cam. The drive stops the axis, and the fault must be acknowledged immediately before a new search for reference can be started. The message carries no fault value, so there is no further decoding.

Why it appears

  • After the search for reference was started, the axis moved through the maximum permissible distance to the reference cam without actually finding the reference cam.

What to check

  1. Check the "reference cam" binector input (BI: p2612) — this is the signal through which the drive is told that the cam has been reached.
  2. Check the maximum permissible distance to the reference cam (p2606); the search ends with this fault when the axis has covered this distance without the cam signal appearing.
  3. If the axis does not have any reference cam, set p2607 to 0.

Parameters the manual names

  • p2612 (Ref_cam) — BI: EPOS search for reference reference cam; the binector input carrying the reference cam signal, checked first when the cam is not found.
  • p2606 (Ref_cam max s) — EPOS search for reference reference cam maximum distance; the maximum distance the axis may cover during the search, checked against the real distance to the cam.
  • p2607 (Ref_cam pres) — EPOS search for reference reference cam present; set to 0 when the axis has no reference cam at all.

Acknowledging and restarting

Acknowledge the fault immediately once it has responded. After the cause has been corrected, start the search for reference again; as long as the cam signal is not found within the distance set in p2606, the fault will come back with the next search.

The same on every family

Every manual that describes F07458 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF1 (OFF2, OFF3)IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2821
G130, G150OFF1 (OFF2, OFF3)IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1558

The drives this code lives on

F07458 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07458 mean on a SINAMICS drive?

The EPOS search for reference moved the axis through the maximum permissible distance without finding the reference cam. The drive stops the axis and the fault must be acknowledged immediately.

Which parameters are checked for F07458?

Check the reference cam binector input p2612 and the maximum permissible search distance p2606. If the axis has no reference cam at all, set p2607 to 0.

How do I clear fault F07458?

Remove the cause first, then acknowledge the fault immediately and start the search for reference again. The fault returns as long as the cam signal is not found within the distance set in p2606.

What do I set when the axis has no reference cam?

Set p2607 to 0. The manual gives this as the remedy when the axis does not have any reference cam.