SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS G130, G150, S120, S150

F07110Drive: Sampling times and basic clock cycle do not match

What it means

F07110 is raised when the sampling times parameterized in the drive do not match the basic clock cycle. The drive tells you which parameter is concerned: r0949, interpreted as a decimal number, contains the number of the parameter involved, and the message text shows it as “Parameter: %1”.

Why it appears

  • The sampling times set in the drive’s parameters do not match the basic clock cycle.

What to check

  1. Note which basic clock cycle is selected — check p0111; the basic sampling times themselves are displayed in r0110.
  2. Enter the current controller sampling times so that they are identical to the basic clock cycle, for example by selecting the matching pre-setting in p0112.
  3. If the sampling times in p0115 are to be changed manually, note that this is only possible when the sampling times pre-setting “Expert” (p0112) is selected.

Reading the message value

  • The fault value is stored in r0949 and is to be interpreted as a decimal number: it specifies the parameter involved — the number of the parameter whose sampling times do not match the basic clock cycle.
  • The message value appears as “Parameter: %1”, where %1 is the parameter concerned.

Parameters the manual names

  • r0949 — fault value: read it as a decimal number to see which parameter this fault refers to.
  • r0110 — basic sampling times (t_basis): displays the basic clock cycle that the set sampling times have to match.
  • r0111 — basic sampling time selection (t_basis sel): shows which basic clock cycle is selected.
  • p0112 — sampling times pre-setting for p0115 (t_sample for p0115): selecting it makes the current controller sampling times identical to the basic clock cycle; its “Expert” setting is the precondition for editing p0115 manually.
  • p0115 — sampling time for supplementary functions (t_samp suppl_fct): holds the sampling times that must match the basic clock cycle.

Acknowledging and restarting

The drive takes no automatic action when this fault occurs. Once the sampling times have been corrected so that they match the basic clock cycle, acknowledge the fault immediately — no other reset procedure is described.

The same on every family

Every manual that describes F07110 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1540
S120, S150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2789

The drives this code lives on

F07110 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F07110 mean?

It means that the parameterized sampling times do not match the basic clock cycle. The fault value in r0949, read as a decimal number, specifies the parameter involved.

How do I fix fault F07110?

Enter the current controller sampling times so that they are identical to the basic clock cycle, e.g. by selecting the matching pre-setting in p0112, and note the basic clock cycle selected in p0111. Then acknowledge the fault immediately.

Why can I not change the sampling times in p0115?

The sampling times in p0115 can only be changed manually when the sampling times pre-setting “Expert” (p0112) is selected.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals