Fault · SINAMICS G130, G150, S120, S150

F07100Drive: Sampling times cannot be reset

What it means

F07100 is raised when a drive parameter reset is started (p0976) and the drive cannot reset the sampling times using p0111, p0112 and p0115. The drive reports the parameter whose setting is blocking the reset: the parameter number is entered as the message value («Parameter: %1») and can be read in r0949.

Why it appears

  • A drive parameter reset (p0976) was started, and the sampling times cannot be reset using p0111, p0112 and p0115.
  • The setting of the parameter named in the fault value prevents the sampling times from being reset.

What to check

  1. Keep the sampling times as they are currently set and continue to work with them.
  2. Alternatively, set the basic clock cycle p0110[0] to the original value before you reset the drive parameters.

Reading the message value

  • Read the fault value in r0949 as a decimal number — the manual gives no bit decoding for this fault.
  • The value is the parameter whose setting prevents the sampling times from being reset.
  • The message value carries the same information as «Parameter: %1», where %1 is that parameter number.

Parameters the manual names

  • p0976 (reset and load all parameters): the drive parameter reset; the fault is raised while this reset is running if the sampling times cannot be reset along with it.
  • p0112 (sampling times pre-setting): one of the sampling-time settings affected by the reset; check this parameter if the fault value points to it.
  • p0115 (sampling time for supplementary functions): one of the sampling-time settings affected by the reset; check this parameter if the fault value points to it.
  • r0949 (fault value): read here as a decimal number to identify the parameter whose setting prevents the sampling time reset.
  • r0110 (basic sampling times): the manual cross-references this display of the basic sampling times for this fault; the associated basic clock cycle p0110[0] must be set back to its original value before the parameter reset.

Acknowledging and restarting

An immediate acknowledgment is sufficient — for example with the acknowledgment command on the operator panel or in the commissioning tool — and the drive does not have to be powered down. The drive takes no automatic action for this fault, so no special restart is needed. Follow one of the two remedies — keep the set sampling times, or set p0110[0] to the original value before the drive parameter reset — and then acknowledge the fault.

What differs between the drive families

Straight from the manuals' own fields — F07100 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1539
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2788

The drives this code lives on

F07100 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07100 on a SINAMICS drive mean?

During a drive parameter reset (p0976) the sampling times cannot be reset using p0111, p0112 and p0115. The fault value in r0949 names the parameter whose setting prevents the reset.

How do I clear fault F07100?

Either continue working with the sampling times as they are set, or set the basic clock cycle p0110[0] to its original value before you reset the drive parameters. The fault is then cleared with an immediate acknowledgment.

How do I find out which parameter is blocking the sampling time reset?

Read the fault value in r0949 as a decimal number; it is the number of the parameter whose setting prevents the sampling times from being reset.

Does F07100 stop the drive?

No, the drive takes no automatic action for this fault. It is acknowledged immediately and the drive does not have to be powered down.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals