Fault · SINAMICS S120, S150

F07093Drive: Test signal error

What it means

F07093 means that the drive identified an error while executing the Test signal function, which is started with p5307.1 = 1 as part of One Button Tuning (OBT). The function was not executed or was canceled. The drive writes the concrete reason into the fault value r0949 (interpret decimal), so the number tells you which of the seven causes applies. Depending on the drive configuration, the same condition can also be signalled as an alarm (A).

Why it appears

  • An error was identified while executing the Test signal function (p5307.1 = 1); the function was not executed or was canceled. The fault value in r0949 distinguishes the seven individual causes listed below.

What to check

  1. Read the fault value in r0949 (interpret decimal) and apply the matching step below.
  2. Fault value 1: define a distance limit (p5308).
  3. Fault value 2: increase the duration or the distance limit (p5309, p5308) so the moment of inertia estimator can stabilize.
  4. Fault value 3: check the distance limit (p5308).
  5. Fault value 4: configure speed control with an encoder.
  6. Fault value 5: increase the distance limit p5308 or reduce the offset p5297. With the factory setting the test signal lasts approximately 1.3 s; an offset of 60 rpm then corresponds to a distance of approximately 1.3 revolutions, so p5308 must be parameterized longer than this distance plus 10% controller reserve (e.g. p5308 = 515°). The required distance also depends on the speed controller sampling time (p0115[1]) and the controller configuration (p5271). Note that this fault value can only be acknowledged after p5300 has been set = 0.
  7. Fault value 6: keep the drive switched on until the "Test signal" function has been completely exited.
  8. Fault value 7: set the speed setpoint to zero; it is possible that the setpoint was entered from the control panel.

Reading the message value

  • 1: No distance limit has been defined (p5308 = 0).
  • 2: The moment of inertia estimator has not stabilized in the parameterized time (p5309) (r1407.26).
  • 3: The parameterized distance (p5308) was exceeded.
  • 4: no motor encoder parameterized (closed-loop speed control without encoder).
  • 5: Offset (p5297) is too high for the parameterized distance (p5308).
  • 6: Pulse enable was withdrawn while traversing.
  • 7: speed setpoint not equal to zero.

Parameters the manual names

  • r0949 — holds the fault value (interpret decimal) that tells which of the seven causes raised F07093.
  • p5307 — activates the One Button Tuning test signal (bit 1 = 1); the function whose failed or canceled run produces this fault.
  • p5308 — One Button Tuning test signal distance limiting: define it (fault value 1), check it (3) or extend it (2 and 5).
  • p5309 — One Button Tuning test signal duration: increase it when the moment of inertia estimator has not stabilized within the parameterized time (fault value 2).
  • p5297 — offset of the test signal: reduce it when it is too high for the parameterized distance (fault value 5).
  • p5300 — autotuning selection: must be set = 0 before a fault value 5 can be acknowledged.
  • p0115[1] — sampling time that influences the distance the test signal needs (fault value 5).
  • p5271 — One Button Tuning configuration that also influences the required distance (fault value 5).

Acknowledging and restarting

Remove the cause first, then acknowledge the fault — acknowledgement is possible immediately, with one exception: a fault value 5 can only be acknowledged after p5300 has been set = 0. When the drive signals the condition only as an alarm (A), no acknowledgement is required. After the correction the test signal function can be started again with p5307.1 = 1.

The same on every family

Every manual that describes F07093 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF3 (NONE, OFF1, OFF2)IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)Control Unit (CU)SINAMICS S120, S150 List Manual · p. 2786

The drives this code lives on

F07093 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07093 mean on a SINAMICS S120 or S150?

The drive detected an error while executing the Test signal function of One Button Tuning, started with p5307.1 = 1; the function was not executed or was canceled. The fault value in r0949 identifies which of the seven causes applied.

Why can F07093 with fault value 5 not be acknowledged?

This fault value can only be acknowledged after p5300 has been set = 0. Before that, extend the distance limit p5308 or reduce the offset p5297.

How large should the distance limit p5308 be for the test signal?

With the factory setting the test signal lasts about 1.3 s, and a 60 rpm offset corresponds to about 1.3 revolutions. p5308 must be longer than this distance plus 10% controller reserve, for example p5308 = 515°.

Can F07093 also be signalled as an alarm?

Yes, depending on the drive configuration the same condition can also appear as an alarm (A), in which case no acknowledgement is needed.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals