What it means
F07011 Drive: Motor overtemperature is raised when the drive judges the motor temperature to be too high. The trigger depends on the sensor that is connected: with a KTY84 or PT1000 sensor (one manual also lists PT100, and the monitoring also runs with no sensor via the model), the measured motor temperature or the model temperature has exceeded the fault threshold (p0605), or the timer (p0606) has expired after the alarm threshold (p0604) was exceeded. With a PTC or bimetallic NC contact, the response threshold of 1650 Ohm was exceeded or the NC contact opened, and the timer (p0606) has expired. The motor temperature model itself can also raise the fault when its calculated temperature is too high. When the fault triggers, the response parameterized in p0610 becomes active: the drive coasts the motor down and must be acknowledged before it will start. The manual specifies a hysteresis of 2K for this monitoring. Where a wire break or a sensor that is not connected is involved with KTY84/PT1000, the manual notes: The alarm is withdrawn if the response threshold for wire breakage or sensor not connected is exceeded (R > 2120 Ohm).
Why it appears
- The motor is overloaded.
- The motor ambient temperature is too high.
- With a PTC or bimetallic NC contact: wire breakage, or the sensor is not connected.
- The motor temperature model is incorrectly parameterized — the manual for the SERVO drive objects names this cause; the other families list only the three above.
What to check
- Reduce the motor load.
- Check the ambient temperature and the motor ventilation.
- Check the wiring and the temperature sensor connection — for a PTC or bimetallic NC contact, the wiring and the connection of the contact.
- Check the monitoring limits (this and the following checks are listed in the manual for the SERVO drive objects; the other families stop after the sensor check).
- Check the encoder type (p0404).
- Check the motor type (p0300, p0301).
- Check the activation of the motor temperature model (p0612).
- Check the motor temperature model parameters.
- Check the encoder (p0404).
Reading the message value
The drive writes the fault value into r0949; interpret it as a decimal number:
- 1, 2, 3, 4: number of the temperature channel leading to the message (for SME/TM120 with p0601 = 10, 11).
- 200: motor temperature model 1 (I2t): temperature too high — the entry for the VECTOR_G drive objects adds the condition p0612.0 = 1, p0611 > 0, p0615 reached.
- 300: motor temperature model 3 — after the monitoring time has expired, the temperature is still higher than the alarm threshold (SERVO drive objects).
- 301: motor temperature model 3 — the temperature is too high, or the model has not been parameterized (SERVO drive objects).
- 302: motor temperature model 3 — the encoder temperature is not within the valid range (SERVO drive objects).
- The values 300, 301 and 302 are printed only in the manual for the SERVO drive objects.
Parameters the manual names
- r0949 — read the fault value here (decimal) to see which temperature channel or model raised the fault.
- p0604 — alarm threshold of the sensor monitoring; the timer p0606 starts once it has been exceeded.
- p0605 — fault threshold; exceeding it raises the fault.
- p0606 — timer whose expiry (after the alarm threshold, or after 1650 Ohm with a PTC/NC contact) triggers the fault.
- p0610 — response the drive activates when the overtemperature is detected.
- p0601 — motor temperature sensor type; the channel-number fault values apply for SME/TM120 with p0601 = 10, 11.
- p4600 ... p4603 — motor temperature sensor type on the SME; with the settings 10, 30 the message follows the 1650 Ohm response threshold, with 12, 32 the timer after 1650 Ohm has been exceeded.
- p4610 ... p4613 — the same sensor types on the TM120 (MDS).
- p0612 — activation of the motor temperature model; check whether it is active (p0612.0 = 1 appears in the condition for fault value 200).
- p0611 — I2t motor model thermal time constant; fault value 200 occurs with p0611 > 0.
- p0615 — I2t fault threshold; fault value 200 is raised once it is reached.
- p0404 — effective encoder configuration; check the encoder type and the encoder here.
- p0300 — motor type selection; check it against the connected motor.
- p0301 — motor code number selection; check it together with p0300.
Acknowledging and restarting
The drive coasts the motor down when this fault triggers and must be acknowledged before it will start. Remove the cause first — for example reduce the motor load or repair the sensor wiring — then acknowledge the fault and restart the drive.
What differs between the drive families
Straight from the manuals' own fields — F07011 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 (NONE, OFF1, OFF3, STOP2) | — | Motor overload (8) | Motor | SINAMICS S120, S150 List Manual · p. 2776 |
| S120, S150 | OFF2 (NONE, OFF1, OFF3, STOP2) | — | Motor overload (8) | Motor | SINAMICS S120, S150 List Manual · p. 2777 |
| G130, G150 | OFF2 (NONE, OFF1, OFF3, STOP2) | IMMEDIATELY | Motor overload (8) | Motor | SINAMICS G130, G150 List Manual · p. 1534 |
| G120XA | OFF2 (NONE, OFF1, OFF3, STOP2) | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1119 |
| G120 | OFF2 (NONE, OFF1, OFF3, STOP2) | IMMEDIATELY | Motor overload (8) | — | SINAMICS G120 · p. 870 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 393 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 384 |
The drives this code lives on
F07011 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07011 mean on a SINAMICS drive?
The drive has detected motor overtemperature. Either the measured or calculated motor temperature exceeded the fault threshold p0605, or the timer p0606 expired after the alarm threshold p0604 was exceeded, or a PTC/bimetallic NC contact passed its 1650 Ohm response threshold or opened.
What fault values are reported with F07011?
Read r0949 as a decimal: 1, 2, 3 or 4 name the temperature channel (for SME/TM120 with p0601 = 10, 11), 200 is motor temperature model 1 (I2t), and 300, 301 and 302 refer to motor temperature model 3 on SERVO drive objects.
How do I clear fault F07011?
Reduce the motor load, check the ambient temperature and the motor ventilation, and check the sensor wiring and connection. Once the cause is removed, acknowledge the fault and restart the drive.
At what resistance does a PTC trigger F07011?
The manual gives a response threshold of 1650 Ohm for a PTC or bimetallic NC contact; the fault follows when the timer p0606 expires. For KTY84/PT1000, the wire-break response threshold is R > 2120 Ohm.