Fault · SINAMICS G120, G120XA, G130, G150, S120, S150

F07080Drive: Incorrect control parameter

What it means

F07080 is raised when the drive checks its closed-loop control parameters and finds one of them set incorrectly. The manual's example is p0356 (motor stator leakage inductance, L_spread) set to 0. The fault value in r0949 contains the number of the parameter involved, so the code identifies exactly which setting to correct; the message value displays it as Parameter: %1.

Why it appears

  • The closed-loop control parameters have been parameterized incorrectly — one of them holds a value the drive cannot use. The example the manual gives is p0356 = L_spread = 0.

What to check

  1. Read the fault value in r0949 and interpret it as a decimal number; it contains the number of the parameter that raised the fault.
  2. Open that parameter and check its setting. The manuals cross-refer the following parameters for this fault: p0310, p0311, p0341, p0344, p0350, p0354, p0356, p0357, p0358, p0360, p0400, p0404, p0408, p0640, p1082 and p1300.
  3. Correct the value the fault points to — the manual's example is p0640 (current limit), which must be set to a value greater than 0.
  4. Acknowledge the fault with a POWER ON.

Reading the message value

  • The fault value is read in r0949 and is to be interpreted as a decimal number; it contains the parameter number involved.
  • The message value is Parameter: %1, where %1 is that parameter number.

Parameters the manual names

  • r0949 (Fault value) — read here, interpreted as a decimal, to see which parameter number triggered F07080.
  • p0356 (Motor stator leakage inductance / Mot L_stator leak) — the manual's example of an incorrect setting is 0 here (p0356 = L_spread = 0).
  • p0640 (Current limit) — the manual's example correction: set the current limit to a value greater than 0.
  • p0310 (Cylinder piston diameter / Cyl piston diam) — check the setting if r0949 names this parameter.
  • p0311 (Cylinder piston rod diameter A side / Cyl PistRodDiam A) — check the setting if r0949 names this parameter.
  • p0341 (Cylinder weight / Cyl weight) — check the setting if r0949 names this parameter.
  • p0344 (Cylinder mounting position A side / Cyl mount pos A) — check the setting if r0949 names this parameter.
  • p0350 (Damping uncontrolled axis / Damp unctrl axis) — check the setting if r0949 names this parameter.
  • p0354 (Axis natural frequency B side / Axis fn B) — check the setting if r0949 names this parameter.
  • p0357 (Motor stator inductance d axis / Mot L_stator d) — check the setting if r0949 names this parameter.
  • p0358 (Motor rotor leakage inductance / damping inductance d axis / Mot L_r leak / LDd) — check the setting if r0949 names this parameter.
  • p0360 (Motor magnetizing inductance/magn. inductance d axis saturated / Mot Lh/Lh d sat) — check the setting if r0949 names this parameter.
  • p0400 (Encoder type selection / Enc_type sel) — check the setting if r0949 names this parameter.
  • p0404 (Encoder configuration effective / Enc_config eff) — check the setting if r0949 names this parameter.
  • p0408 (Rotary encoder pulse number / Rot enc pulse no) — check the setting if r0949 names this parameter.
  • p1082 (Maximum velocity / v_max) — check the setting if r0949 names this parameter.
  • p1300 (Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode) — check the setting if r0949 names this parameter.

Acknowledging and restarting

Correct the parameter named in r0949 first, then acknowledge the fault. The manuals specify acknowledgement IMMEDIATELY with POWER ON, i.e. the fault is cleared by switching the drive off and on again once the parameter has been corrected.

What differs between the drive families

Straight from the manuals' own fields — F07080 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2781
G130, G150NONEIMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1536
G120NONEIMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 872
G120XANONEIMMEDIATELY (POWER ON)SINAMICS G120XA PN converter · p. 1121

The drives this code lives on

F07080 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F07080 mean?

It means a closed-loop control parameter has been parameterized incorrectly, for example a motor data parameter set to 0. The number of the parameter involved is stored in the fault value r0949.

How do I clear fault F07080?

Read the parameter number from r0949 (interpret it as a decimal), correct that parameter — the manual's example is p0640, the current limit, which must be greater than 0 — and then acknowledge the fault with POWER ON.

Which parameters can trigger F07080?

The manuals cross-refer p0310, p0311, p0341, p0344, p0350, p0354, p0356, p0357, p0358, p0360, p0400, p0404, p0408, p0640, p1082 and p1300 for this fault; the example given is p0356 (motor stator leakage inductance) set to 0.

Where does F07080 show which parameter is wrong?

In the fault value r0949, interpreted as a decimal number. The message value also shows it as 'Parameter: %1'.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.