Fault · SINAMICS G130, G150, S120, S150

F06000Infeed: Precharging monitoring time expired

What it means

After the line contactor closes, the power unit of the infeed precharges the DC link and must signal READY within the monitoring time p0857. F06000 is raised when this READY signal does not arrive within that time — the end of the DC link precharging could not be completed. The drive coasts down and must be acknowledged immediately before it will start again. No fault value is supplied with this message.

Why it appears

  • 1) No line supply voltage is connected.
  • 2) The line contactor or the line-side switch has not been closed.
  • 3) The line supply voltage is too low.
  • 4) The line supply voltage is incorrectly set in p0210, so the setting does not match the actual supply.
  • 5) The precharging resistors have overheated because there were too many precharging operations per time unit.
  • 6) The precharging resistors have overheated because the DC link capacitance is too high.
  • 7) The precharging resistors have overheated because power is being taken from the DC link while the infeed unit is not signalling ready for operation (r0863.0).
  • 8) The precharging resistors have overheated because the line contactor was closed during the DC link fast discharge through the Braking Module.
  • 9) The DC link has a ground fault or a short-circuit.
  • 10) The precharging circuit is possibly defective — this applies only to chassis units.

What to check

  1. Check the line supply voltage at the connecting terminals.
  2. Check the line supply voltage setting in p0210.
  3. Check the monitoring time in p0857 and, if required, increase it.
  4. Observe any additional power unit messages and signals, for example F30027, that narrow the cause down.
  5. On booksize units, wait about 8 minutes until the precharging resistors have cooled down before a new attempt; preferably disconnect the infeed unit from the line supply while waiting.
  6. If cause 5 applies, carefully observe the permissible precharging frequency (refer to the appropriate Equipment Manual).
  7. If cause 6 applies, check the total capacitance of the DC link and reduce it to the maximum permissible DC link capacitance if necessary (refer to the appropriate Equipment Manual).
  8. If cause 7 applies, interconnect the ready-for-operation signal of the infeed unit (r0863.0) in the enable logic of the drives connected to this DC link.
  9. If cause 8 applies, check the connections of the external line contactor; the line contactor must be open during DC link fast discharge.
  10. If cause 9 applies, check the DC link for ground faults or short-circuits.

Parameters the manual names

  • p0857 (power unit monitoring time, PU t_mon) — the time within which the power unit must signal READY after the line contactor closes; for F06000, check this time and increase it if required.
  • p0210 (drive unit line supply voltage, U_connect) — the line supply voltage the drive is set for; for F06000, check that this setting matches the voltage actually connected.

Acknowledging and restarting

Remove the cause first, then acknowledge the fault; the acknowledgement must follow immediately. The drive coasts down and will not start again until F06000 has been acknowledged. If the precharging resistors may have overheated (booksize units), let them cool for about 8 minutes with the infeed unit disconnected from the line supply before the next start attempt.

The same on every family

Every manual that describes F06000 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2 (OFF1)IMMEDIATELYInfeed faulted (13)Power ModuleSINAMICS S120, S150 List Manual · p. 2754
G130, G150OFF2 (OFF1)IMMEDIATELYInfeed faulted (13)Power ModuleSINAMICS G130, G150 List Manual · p. 1526

The drives this code lives on

F06000 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F06000 mean on a SINAMICS infeed?

The power unit did not signal READY within the monitoring time p0857 after the line contactor closed, so the end of the DC link precharging could not be completed.

Why do the precharging resistors overheat and trigger F06000?

Four situations lead to overheated precharging resistors: too many precharging operations per time unit, a DC link capacitance that is too high, power being taken from the DC link while the infeed unit is not ready for operation (r0863.0), and the line contactor being closed during DC link fast discharge through the Braking Module.

How long must I wait before a new start attempt after F06000?

On booksize units, wait about 8 minutes until the precharging resistors have cooled down, preferably with the infeed unit disconnected from the line supply.

How is F06000 cleared and acknowledged?

Remove the cause first, then acknowledge the fault immediately; the drive coasts down and will not start again until the fault has been acknowledged.