Fault · SINAMICS S120, S150

F06200Infeed: One or several line phases failed

What it means

F06200 reports that the infeed has detected a failure or an overvoltage in one or several line supply phases. The drive raises the fault either during the switch-on phase of the infeed or while the infeed is operational. When it trips, the infeed coasts down and must be acknowledged before it will start again.

Why it appears

  • The fault can be raised in two operating states: during the switch-on phase of the infeed, or while the infeed is operational.
  • At switch-on: the measured line supply angle deviates from the regular characteristic of a 3-phase system, so the PLL cannot be synchronized.
  • At switch-on with a Voltage Sensing Module (VSM): the fault appears immediately after switch-on if the phase assignment L1, L2, L3 at the VSM differs from the phase assignment at the power unit.
  • During operation: an additional fault occurred while the line voltage alarm (A06205) or the current symmetry alarm (A06206) was active, and this additional fault led to the shutdown; the alarm values of A06205 and A06206 can provide additional information about the cause.
  • Possible underlying causes named for this fault: a voltage dip on the line side, a phase failure, or an overvoltage lasting longer than 10 ms.
  • An overload condition on the load side with peak current.
  • A missing line reactor.

What to check

  1. Check the line supply, the terminals and the fuses.
  2. Check the connection and the size (rating) of the line filter and/or the line commutating reactor.
  3. Check and correct the phase assignment at the VSM (X521 or X522) and at the power unit.
  4. Check the load.
  5. If the infeed failed during operation, carefully note the previous alarm messages A06205/A06206 together with their alarm values.

Parameters the manual names

  • p3463 (Infeed phase failure detection line supply angle change, INF ph_fail phi) — the line supply angle change parameter of the infeed's phase-failure detection, which the manual names as a reference for this fault.

Acknowledging and restarting

The infeed trips and coasts down when this fault is raised and starts again only after the fault has been acknowledged. Acknowledge the fault immediately; in the alternative response, the acknowledgement is carried out by switching the drive's power supply off and on again.

The same on every family

Every manual that describes F06200 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2 (OFF1)IMMEDIATELY (POWER ON)Network fault (2)NoneSINAMICS S120, S150 List Manual · p. 2757

The drives this code lives on

F06200 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F06200 mean on a SINAMICS infeed?

It reports a failure or an overvoltage on one or several line supply phases. The infeed coasts down and the fault must be acknowledged before the drive restarts.

Why does F06200 appear immediately after switching on?

The measured line supply angle then deviates from the regular characteristic of a 3-phase system, so the PLL cannot be synchronized. With a Voltage Sensing Module (VSM), the phase assignment L1, L2, L3 at the VSM may also differ from the assignment at the power unit.

How do I clear fault F06200?

Check the line supply, terminals and fuses, and the connection and size (rating) of the line filter and/or line commutating reactor. Then correct the phase assignment at the VSM (X521 or X522) and at the power unit, check the load, and acknowledge the fault.

What do alarms A06205 and A06206 have to do with F06200?

If the infeed failed during operation, this fault followed an active line voltage alarm (A06205) or current symmetry alarm (A06206). Their alarm values can provide additional information about the cause of the shutdown.