What it means
The safety monitoring channel has identified an incorrect configuration setting for the "Safe synchronous position via PROFIsafe" function: the settings in the PROFIBUS/PROFINET controller are not permissible for this function. The fault can only occur when the function is enabled (p9501.29 = 1). The drive coasts down and performs a STOP A; it restarts only after the impermissible setting has been corrected and the fault has been acknowledged.
Why it appears
- An incorrect configuration setting was identified for the "Safe synchronous position via PROFIsafe" function, which is enabled (p9501.29 = 1).
- Fault value 1: the function is enabled but is not set according to the rule Tdp = 2 x n x p9500 (n = 1, 2, 3, ...) — the bus cycle time Tdp and the monitoring clock cycle p9500 do not fit together.
- Fault value 2: isochronous operation is not set on the PROFIBUS/PROFINET controller.
What to check
- Read the fault value in r0949 (interpret decimal) to see which of the two settings is impermissible.
- Fault value = 1: set the bus cycle time Tdp and the monitoring clock cycle p9500 according to the rule Tdp = 2 x n x p9500 (n = 1, 2, 3, ...).
- Fault value = 2: set "Isochronous mode" on the PROFIBUS/PROFINET controller.
Reading the message value
- The drive enters the fault value in r0949; interpret it in decimal.
- 1: "Synchronous safe position via PROFIsafe" is enabled (p9501.29 = 1) and is not set according to the rule Tdp = 2 x n x p9500 (n = 1, 2, 3, ...).
- 2: "Synchronous safe position via PROFIsafe" is enabled (p9501.29 = 1) and isochronous operation is not set.
- STO: Safe Torque Off
Parameters the manual names
- r0949 — read the fault value here (decimal) to determine which of the two impermissible settings triggered the fault.
- p9501 — p9501.29 = 1 shows that "Synchronous safe position via PROFIsafe" is enabled; the fault only occurs when this bit is set.
- p9500 — the SI Motion monitoring clock cycle: set it so that, together with the bus cycle time Tdp, the rule Tdp = 2 x n x p9500 (n = 1, 2, 3, ...) is fulfilled.
- p9507 — p9507.0 = 1 activates the "Extended message acknowledgment", which additionally permits acknowledging the STOP A by an internal event acknowledge.
Acknowledging and restarting
This fault results in a STOP A. The manual gives two ways to acknowledge the STOP A: select STO and then deselect again
, or an internal event acknowledge — the latter requires that the "Extended message acknowledgment" is active (p9507.0 = 1). After the impermissible setting in the PROFIBUS/PROFINET controller has been corrected, acknowledge the fault immediately or by POWER ON; the drive starts again once the fault is no longer present.
The same on every family
Every manual that describes F01675 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | Control Unit (CU) | SINAMICS S120, S150 List Manual · p. 2652 |
The drives this code lives on
F01675 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F01675 mean on a SINAMICS drive?
The safety monitoring channel has found an incorrect configuration setting for the "Safe synchronous position via PROFIsafe" function: the settings in the PROFIBUS/PROFINET controller are not permissible. The drive coasts down and performs a STOP A.
How do I clear F01675 with fault value 1?
Set the bus cycle time Tdp and the monitoring clock cycle p9500 so that the rule Tdp = 2 x n x p9500 (n = 1, 2, 3, ...) is fulfilled, then acknowledge the fault.
What does fault value 2 of F01675 indicate?
That "Synchronous safe position via PROFIsafe" is enabled (p9501.29 = 1) but isochronous operation is not set. Set "Isochronous mode" on the PROFIBUS/PROFINET controller.
How is F01675 acknowledged?
The resulting STOP A is acknowledged by selecting STO and then deselecting it again, or by an internal event acknowledge when p9507.0 = 1 ("Extended message acknowledgment" active). After the cause is removed, the fault itself is acknowledged immediately or by POWER ON.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.