Fault · SINAMICS G130, G150, S120, S150

F01679SI CU: Safety parameter settings and topology changed, warm restart/POWER ON

What it means

The manuals describe this fault as SI CU: Safety parameter settings and topology changed, warm restart/POWER ON. It is raised in two steps: safety parameters have been changed, and such changes only take effect after a warm restart or a POWER ON — the cause text refers to alarm A01693 in this context. Despite that, a partial power up (boot) was then performed with the modified configuration. While the fault is active the drive coasts down and only starts again once the changed settings have been activated by the required restart.

Why it appears

  • Safety parameters have been changed; these changes only take effect after a warm restart or a POWER ON. The drive's cause text refers here to alarm A01693.
  • A partial power up (boot) was then performed with the modified configuration, i.e. before the required warm restart or POWER ON had been carried out.

What to check

  1. Carry out a warm restart: set p0009 = 30 and run the reset via p0976 with the value 2 or 3.
  2. Alternatively, carry out a POWER ON: switch the power supply off and on again for all components.

Parameters the manual names

  • p0009 — device commissioning parameter filter (Dev com par_filt): set to 30 for the warm restart that activates the changed safety parameters.
  • p0976 — reset and load all parameters (Reset load all par): run with the value 2 or 3 to carry out the warm restart named in the remedy.

Acknowledging and restarting

Both remedies activate the changed safety parameters and clear the fault: the warm restart with p0009 = 30 and p0976 = 2 or 3, or a POWER ON (switch-off/switch-on) for all components. The drive accepts a new start command only after this acknowledgement, so the restart must actually be performed before the drive can run again.

The same on every family

Every manual that describes F01679 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2 (OFF1, OFF3)POWER ONError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2652
G130, G150OFF2 (OFF1, OFF3)POWER ONError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1450

The drives this code lives on

F01679 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01679 mean in SINAMICS?

Safety parameters were changed, and although they only take effect after a warm restart or POWER ON, a partial power up (boot) was then performed with the modified configuration. The drive coasts down until the required restart is done.

How do I clear fault F01679?

Carry out a warm restart with p0009 = 30 and p0976 = 2 or 3, or switch the power supply off and on again for all components. The changed safety parameters then take effect and the fault can be cleared.

Can I acknowledge F01679 without a POWER ON?

The manual lists exactly two ways: the warm restart with p0009 = 30 and p0976 = 2 or 3, and the POWER ON (switch-off/switch-on) for all components. No panel reset is named for this fault.

What is the difference between A01693 and F01679?

The cause text of F01679 refers to alarm A01693, which accompanies changed safety parameters that still need a warm restart or POWER ON to take effect. F01679 follows when a partial boot was then carried out with the modified configuration.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.