Fault · SINAMICS G120, G120C, G130, G150, S120, S150

F01625SI P1 (CU): Sign-of-life error in safety data

What it means

F01625 is raised when the drive-integrated 'Safety Integrated' (SI) function on processor 1 (P1) of the Control Unit (CU) detects an error in the sign-of-life of the safety data; the function then initiates a STOP A. The monitoring watches the exchange of safety data between the two monitoring channels — the G120 manual places this exchange between processor 1 and processor 2, the manuals for the other families between the two monitoring channels of the safety function. The motor coasts down (OFF2), and the fault must be acknowledged with a POWER ON before the drive will start again.

Why it appears

  • The communication of the safety data between the two monitoring channels has failed or is faulty: for S120, S150, G130 and G150 the manual describes a DRIVE-CLiQ communication error or a total communication failure between the two monitoring channels, for the G120 a communication error between processor 1 and processor 2.
  • A time slice overflow of the safety software has occurred.

What to check

  1. Select STO (Safe Torque Off) and then deselect it again.
  2. Carry out a POWER ON (switch-off/switch-on) of all components; on the G120C the manual says to switch the converter power supply off and on again.
  3. Check whether additional faults are present and, if required, perform diagnostics. On S120, S150, G130 and G150 this check is aimed specifically at a DRIVE-CLiQ communication error between the two monitoring channels.
  4. Deselect all drive functions that are not absolutely necessary and reduce the number of drives (S120, S150, G130, G150).
  5. Check the electrical cabinet design and cable routing for EMC compliance.
  6. Check whether an impermissible voltage is connected at one of the digital outputs (G120, G120C).
  7. Check whether a digital output is loaded with an impermissible current (G120, G120C).

Reading the message value

  • The drive writes the fault value into r0949; the manual says to interpret it as a decimal number.
  • No decoding of the value is published — the manual states it is Only for internal Siemens troubleshooting.

Parameters the manual names

  • r0949 — fault value of this message: read it out and interpret it as a decimal number; the manual notes it serves only internal Siemens troubleshooting and publishes no decoding.

Acknowledging and restarting

The fault must be acknowledged immediately, and acknowledgement is a POWER ON: switch off and switch on all components (on the G120C, the converter power supply). The first remedy step before this is to select STO and then deselect it again. While the fault is present the drive coasts down (OFF2) and will not start again until the fault has been acknowledged.

What differs between the drive families

Straight from the manuals' own fields — F01625 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELY (POWER ON)Internal (DRIVE-CLiQ) communication error (12)NoneSINAMICS S120, S150 List Manual · p. 2626
G130, G150OFF2IMMEDIATELY (POWER ON)Internal (DRIVE-CLiQ) communication error (12)NoneSINAMICS G130, G150 List Manual · p. 1431
G120OFF2IMMEDIATELY (POWER ON)Internal (DRIVE-CLiQ) communication error (12)SINAMICS G120 · p. 839
G120CSINAMICS G120C Converters · p. 382

The drives this code lives on

F01625 is described for G120, G120C, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01625 mean on a SINAMICS drive?

The Safety Integrated function on processor 1 of the Control Unit has detected an error in the sign-of-life of the safety data and has initiated a STOP A. The drive coasts down (OFF2).

How do I clear F01625?

Select STO and then deselect it again, and carry out a POWER ON (switch-off/switch-on) of all components — on the G120C, of the converter power supply. The fault is acknowledged by this power cycle.

What causes F01625?

Either the communication of the safety data between the two monitoring channels (on the G120: between processor 1 and processor 2) has failed or is faulty, or a time slice overflow of the safety software has occurred.

What is the fault value of F01625?

The drive stores it in r0949 and it is interpreted as a decimal number. The manual publishes no decoding because the value is used only for internal Siemens troubleshooting.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals