What it means
F01380 is raised when the drive, while detecting the actual topology, identifies a component with a defective EEPROM. The G130/G150 and S120/S150 list manuals describe this fault identically, so the cause and remedy below apply unchanged. The drive stores a fault value in r0949 that names the defective component by its preliminary component number, and the operator panel or commissioning tool shows the message value Preliminary component number: %1
. The fault triggers no automatic drive response — the remedy is to read out the fault value and remove the component it points to.
Why it appears
- While detecting the actual topology, the drive detected a component with a defective EEPROM.
What to check
- Output the fault value: read r0949 and interpret the value in hexadecimal — it has the structure bbbbaaaa hex, where aaaa is the preliminary component number of the defective components and bbbb is reserved.
- Remove the defective component identified by this preliminary component number.
Reading the message value
The drive stores the fault value in r0949 and it must be interpreted in hexadecimal. The message value Preliminary component number: %1
shows that the drive fills the placeholder %1 with the preliminary component number of the defective component. The fault value decodes as follows:
- bbbbaaaa hex — bbbb = reserved
- aaaa = preliminary component number of the defective components
Parameters the manual names
- r0949 — fault value: for this code, read it out and interpret it in hexadecimal; the aaaa portion of the bbbbaaaa hex value gives the preliminary component number of the defective component.
Acknowledging and restarting
This fault is acknowledged with POWER ON — the drive has to be switched off and on again; an acknowledge command alone does not clear it. Because the drive does not trip automatically when the fault appears, the practical sequence is: read the preliminary component number from r0949, remove the defective component, and then power the drive down and up again to acknowledge the fault.
The same on every family
Every manual that describes F01380 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | POWER ON | Hardware/software error (1) | None | SINAMICS G130, G150 List Manual · p. 1411 |
| S120, S150 | NONE | POWER ON | Hardware/software error (1) | None | SINAMICS S120, S150 List Manual · p. 2601 |
The drives this code lives on
F01380 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F01380 mean on a SINAMICS drive?
It means that while detecting the actual topology, the drive found a component with a defective EEPROM. The fault value in r0949 identifies that component by its preliminary component number.
How do I find the defective component when F01380 appears?
Read the fault value in r0949 and interpret it in hexadecimal: in the bbbbaaaa hex value, aaaa is the preliminary component number of the defective components and bbbb is reserved.
Does F01380 stop the drive?
No. The fault raises no automatic drive response; the defective component only has to be identified via r0949 and removed.
How do I clear fault F01380?
Remove the defective component and then acknowledge the fault by powering the drive down and up again (POWER ON); an acknowledge command alone does not clear it.