SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS G130, G150, S120, S150

F01356Topology: There is a defective DRIVE-CLiQ component

What it means

F01356 is raised when the actual topology indicates at least one defective DRIVE-CLiQ component. While the fault is active, the pulse enable is withdrawn and prevented. The fault value stored in r0949 shows at which connection and component the defective component is connected and which fault cause the drive detected, so it is the starting point for locating the fault.

Why it appears

  • The actual topology indicates at least one defective DRIVE-CLiQ component.
  • Depending on the fault cause stored in the fault value, either a component at this Control Unit is not permissible, or a component has a communication defect.

What to check

  1. Read the fault value in r0949 and interpret it hexadecimal as zzyyxx.
  2. Take zz as the connection number and yy as the component number of the component at which the defective component is connected.
  3. Determine the fault cause from xx: xx = 1 means the component at this Control Unit is not permissible, xx = 2 means the component has a communication defect.
  4. Replace the defective component identified this way and restart the system.

Reading the message value

  • The message value consists of: fault cause %1, component number %2, connection number %3.
  • Fault value (r0949, interpret hexadecimal): zzyyxx hex.
  • zz = connection number of the component at which the defective component is connected.
  • yy = component number of the component at which the defective component is connected.
  • xx = fault cause: xx = 1: component at this Control Unit not permissible; xx = 2: component with communication defect.

Parameters the manual names

  • r0949 (fault value): read the value stored here for this fault and interpret it hexadecimal as zzyyxx to obtain the connection number, the component number and the fault cause.

Acknowledging and restarting

Acknowledge the fault immediately. Because the pulse enable is withdrawn and prevented while the fault is present, the drive only returns to service once the remedy is carried out: Replace the defective component and restart the system.

The same on every family

Every manual that describes F01356 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONE (OFF2)IMMEDIATELYHardware/software error (1)NoneSINAMICS G130, G150 List Manual · p. 1407
S120, S150NONE (OFF2)IMMEDIATELYHardware/software error (1)NoneSINAMICS S120, S150 List Manual · p. 2596

The drives this code lives on

F01356 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01356 mean on a SINAMICS drive?

The actual topology indicates at least one defective DRIVE-CLiQ component. While the fault is active, the pulse enable is withdrawn and prevented.

How do I locate the defective component for F01356?

Read the fault value in r0949 and interpret it hexadecimal as zzyyxx: zz is the connection number and yy the component number at which the defective component is connected.

What do the fault causes 1 and 2 in F01356 mean?

A fault cause of xx = 1 means the component at this Control Unit is not permissible; xx = 2 means a component with a communication defect.

How do I clear fault F01356?

Replace the defective component and restart the system, acknowledging the fault immediately.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals