Fault · SINAMICS G130, G150, S120, S150

F01359Topology: DRIVE-CLiQ performance not sufficient

What it means

F01359 reports that the DRIVE-CLiQ performance on one line is not sufficient to identify a component that has been inserted on that line. It belongs to the group of topology messages. The list manuals for G130/G150 and for S120/S150 describe the fault with an identical cause and an identical remedy, so everything below applies to all four families alike.

Why it appears

  • The performance of one DRIVE-CLiQ line is not sufficient to identify a component that has been inserted on that line.

What to check

  1. Carry out a POWER ON: switch the drive off and then on again.
  2. If several components are concentrated on one DRIVE-CLiQ line, distribute them across several DRIVE-CLiQ lines.

For work on this topology the manual adds a caution: For this topology, do not withdraw and insert components in operation.

Reading the message value

  • The drive stores the fault value in r0949, to be interpreted hexadecimal; the message itself displays this value via a placeholder.
  • No decoding is published: the manual states the value is only for internal Siemens troubleshooting, so there is nothing for you to evaluate on site.

Parameters the manual names

  • r0949 — fault value: for F01359 the drive enters the diagnostic value here in hexadecimal form; the manual reserves it for internal Siemens troubleshooting, so no evaluation is required on site.

Acknowledging and restarting

Acknowledge the message immediately; the drive does not execute any automatic shutdown response to this fault. Because the cause lies in the DRIVE-CLiQ topology, acknowledging alone does not settle the matter: the fault is cleared by carrying out a POWER ON (switch-off/switch-on) and, if required, redistributing the components across several DRIVE-CLiQ lines as described above.

The same on every family

Every manual that describes F01359 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2597
G130, G150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1408

The drives this code lives on

F01359 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01359 on a SINAMICS drive mean?

The drive has found that the performance of one DRIVE-CLiQ line is not sufficient to identify a component that was inserted on that line. It is one of the topology messages and is described identically for G130, G150, S120 and S150.

How do I clear F01359?

Carry out a POWER ON — switch the drive off and on again — and, if several components share one DRIVE-CLiQ line, distribute them across several lines. Then acknowledge the message.

What fault value does F01359 store in r0949?

The value is to be interpreted hexadecimal, but no decoding is published: the manual states it is only for internal Siemens troubleshooting, so there is nothing to evaluate on site.

May I plug or unplug DRIVE-CLiQ components while the drive is running?

No. For this topology the manual explicitly says not to withdraw and insert components in operation.