Fault · SINAMICS G120, G120XA, G130, G150, S120, S150

F01010Drive type unknown

What it means

F01010 is raised when the drive finds a drive type it does not know: the Power Module in use reports a type that the firmware cannot assign to any known drive type. The manuals describe the fault the same way for all the families listed on this page.

Why it appears

  • An unknown drive type was found.

What to check

  1. Replace the Power Module.
  2. Carry out a POWER ON: switch the components off and back on again — the entries that qualify this specify it for all components.
  3. Upgrade the firmware to a later version.
  4. If the fault remains, contact Technical Support.

Reading the message value

  • The fault value is held in r0949 and must be interpreted as a decimal number.
  • The value is the drive object number — match it against p0101 and p0107.
  • The entries for G120 and G120XA print no fault value.

Parameters the manual names

  • r0949 — fault value: read it as a decimal number to obtain the drive object number reported with F01010.
  • p0101 — drive object numbers (DO numbers): the list against which the value in r0949 is matched.
  • p0107 — drive object type (DO type): shows which type is assigned to the drive object named by the fault value.

Acknowledging and restarting

Acknowledge the fault directly after it appears. The POWER ON (switch-off/switch-on) listed under the remedy also clears the message once the cause has been removed.

What differs between the drive families

Straight from the manuals' own fields — F01010 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1372
S120, S150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2558
G120NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 821
G120XANONEIMMEDIATELYSINAMICS G120XA PN converter · p. 1098

The drives this code lives on

F01010 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01010 mean on a SINAMICS drive?

It means the drive has found a drive type it does not know — the Power Module in use reports a type that the firmware cannot assign.

How do I clear F01010?

Replace the Power Module if required, carry out a POWER ON (switch-off/switch-on) and upgrade the firmware to a later version. If the fault remains, contact Technical Support.

How can I see which drive object F01010 refers to?

Read the fault value in r0949 as a decimal number: it contains the drive object number, which you can look up in p0101 and p0107.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.