What it means
C01706 is raised by the SI Motion monitoring functions of the Control Unit when, after a safe stop or a speed changeover has been initiated, the actual speed leaves the band the drive tolerates — either the Safe Acceleration Monitor (SAM) or the Safe Brake Ramp (SBR) limit was exceeded. Which of the two monitors depends on the setting of p9506: motion monitoring with an encoder, encoderless SAM, or encoderless SBR. The exceeded tolerance causes the drive to shut itself down with C01700 "SI Motion: STOP A initiated".
Why it appears
- Motion monitoring functions with an encoder (p9506 = 0), or encoderless with acceleration monitoring SAM set (p9506 = 3): after STOP B (SS1) or STOP C (SS2) was initiated, the speed has exceeded the selected tolerance.
- Motion monitoring functions encoderless with brake ramp monitoring SBR set (p9506 = 1): after STOP B (SS1) or an SLS changeover to the lower speed level, the speed has exceeded the selected tolerance.
- The drive is shut down by message C01700 "SI Motion: STOP A initiated".
What to check
- Check the braking behavior after the stop or the SLS changeover was initiated, i.e. whether the speed overshoots the tolerated band.
- If necessary, adapt the parameter settings of the SAM or SBR function: the SAM actual velocity tolerance p9548, and for SBR the brake ramp reference value p9581, the brake ramp delay time p9582 and the brake ramp monitoring time p9583.
Parameters the manual names
- p9506 — SI Motion function specification (Control Unit): its setting decides which monitoring raises this message — encoder-based monitoring (0), SBR (1) or SAM (3).
- p9548 — SI Motion SAM actual velocity tolerance (Control Unit): the speed tolerance whose exceedance triggers C01706 when SAM is active; adapt it if the braking overshoots after a stop.
- p9581 — SI Motion brake ramp reference value (Control Unit): reference value of the brake ramp SBR monitors; check it against the actual braking when the message comes from SBR.
- p9582 — SI Motion brake ramp delay time (Control Unit): delay time of the monitored brake ramp, one of the SBR settings to adapt after this message.
- p9583 — SI Motion brake ramp monitoring time (Control Unit): monitoring time of the brake ramp, one of the SBR settings to adapt after this message.
Acknowledging and restarting
After the cause has been corrected, the message can be acknowledged without a POWER ON (safe acknowledgment) via the Terminal Module 54F (TM54F), the onboard F-DI (only CU310-2), PROFIsafe or the machine control panel; one manual additionally names acknowledgment using "Acknowledge internal event". Because the drive was shut down through C01700 "SI Motion: STOP A initiated", it only runs again once this safety message has been safely acknowledged.
What differs between the drive families
Straight from the manuals' own fields — C01706 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | None | SINAMICS G130, G150 List Manual · p. 1463 |
| S120, S150 | NONE | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | None | SINAMICS S120, S150 List Manual · p. 2675 |
| G120 | NONE | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | — | SINAMICS G120 · p. 852 |
| S120, S150 | NONE | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | None | SINAMICS S120, S150 List Manual · p. 2676 |
The drives this code lives on
C01706 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does C01706 SI Motion P1 (CU): SAM/SBR limit exceeded mean?
The SI Motion monitoring in the Control Unit detected that, after STOP B (SS1), STOP C (SS2) or an SLS changeover to the lower speed level, the speed exceeded the selected tolerance. The drive is then shut down by C01700 "SI Motion: STOP A initiated".
How can I acknowledge C01706 without a POWER ON?
By safe acknowledgment via the Terminal Module 54F (TM54F), the onboard F-DI (only CU310-2), PROFIsafe or the machine control panel. One manual also names acknowledgment using "Acknowledge internal event".
Which parameters belong to C01706?
p9506 selects which monitoring function is active — encoder-based, SBR or SAM. p9548 holds the SAM actual velocity tolerance, while p9581, p9582 and p9583 parameterize the SBR brake ramp.
Why did my drive shut down when C01706 appeared?
Because the exceeded SAM or SBR limit initiates the shutdown via C01700 "SI Motion: STOP A initiated". After adapting the braking behavior, the safety message must be safely acknowledged.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the C01xxx group · SINAMICS manuals · Siemens manuals