What it means
C01712 is a safety message from the SI Motion monitoring in the Control Unit (CU): while cross checking and comparing its two monitoring channels, the drive detected a difference between parameters or results of the F-IO processing and initiated STOP F. One of the monitoring functions no longer reliably functions - i.e. safe operation is no longer possible.
Two accompanying messages follow: C01711 is displayed with message value 0 because STOP F was initiated, and if at least one monitoring function is active, C01701 “SI Motion: STOP B initiated” is output (in the manuals for S120/S150 and G130/G150 after the parameterized timer has expired). The message value of C01712 itself is read in r9749 (S120/S150 and G130/G150) or r2124 (G120), interpreted decimal, and names the cross-compared data that triggered the message.
Why it appears
- The two monitoring channels disagree: cross checking and comparing found a difference between parameters or results of the F-IO processing.
- The drive treats this as a failure of a monitoring function — it no longer functions reliably, so safe operation is no longer possible — and initiates STOP F.
- The affected data can be any of the cross-compared SI data of the two processors: F-DI terminal selections (STO, SS1, SS2, SOS, SLS, SDI, SLP), discrepancy, debounce and test-stop times, PROFIsafe F-DI transfer, F-DO signal sources and test sensor feedback, plus internal readback, initialization and retraction data — the message value names the data set concerned.
What to check
- Read the message value in r9749 (S120/S150 and G130/G150) or r2124 (G120), interpret decimal, and use the decoding below to identify the cross-compared data that triggered the message.
- Check the parameterization in the parameters involved and correct it if required.
- Ensure equality by copying the SI data to the second channel — the G120 manual says: to processor 2 — and then carry out an acceptance test.
- In the manuals for S120/S150 and G130/G150, check the monitoring clock cycle in p9500 and p9300 for equality.
Reading the message value
The drive enters the number of the cross-compared data that resulted in this message into the message value; read it in r9749 (S120/S150 and G130/G150) or r2124 (G120) and interpret it decimal:
- 1: SI discrepancy monitoring time inputs (p10002, p10102).
- 2: SI acknowledgment internal event input terminal (p10006, p10106).
- 3: SI STO input terminal (p10022, p10122).
- 4: SI SS1 input terminal (p10023, p10123).
- 5: SI SS2 input terminal (p10024, p10124).
- 6: SI SOS input terminal (p10025, p10125).
- 7: SI SLS input terminal (p10026, p10126).
- 8: SI SLS_Limit(1) input terminal (p10027, p10127).
- 9: SI SLS_Limit(2) input terminal (p10028, p10128).
- 10: SI Safe State signal selection (p10039, p10139).
- 11: SI F-DI input mode (p10040, p10140).
- 12: SI F-DO 0 signal sources (p10042, p10142).
- 13: Different states for static inactive signal sources (p10006, p10022 ... p10031).
- 14: SI discrepancy monitoring time outputs (p10002, p10102).
- 15: SI acknowledgment internal event (p10006, p10106).
- 16: SI test sensor feedback signal test mode selected for test stop (p10046, p10146, p10047, p10147).
- 17: SI delay time for test stop at DOs (p10001).
- 18 ... 25: SI test sensor feedback signal (p10046, p10146, p10047, p10147) — expected state of the internal readback signal, generated from the selected test stop mode.
- 26 ... 33: SI test sensor feedback signal (p10046, p10146, p10047, p10147) — expected state of the external readback signal, generated from the selected test stop mode.
- 34 ... 41: SI test sensor feedback signal (p10046, p10146, p10047, p10147) — expected state of the second internal readback signal, generated from the selected test stop mode.
- 42: Internal data for processing the second internal readback signal, generated from the selected test stop mode (p10047, p10147).
- 43: Internal data for processing the internal readback signal, generated from the selected test stop mode (p10047, p10147).
- 44: Internal data for processing the external readback signal, generated from the selected test stop mode (p10047, p10147).
- 45: Internal data for initialization state of test stop mode, dependent upon test stop parameters.
- 46: SI digital inputs debounce time (p10017, p10117).
- 47: Selection F-DI for PROFIsafe (p10050, p10150).
- 48: Screen form of the F-DIs used (p10006, p10022 ... p10031).
- 49: SI SDI positive input terminal (p10030, p10130).
- 50: SI SDI negative input terminal (p10031, p10131).
- 51: SI SLP input terminal (p10032, p10132).
- 52: SI SLP select input terminal (p10033, p10133).
- 53: Internal data for retraction logic (p10009, p100109).
- 54: SI F-DI for retraction SLP (p10009, p100109).
Scope on G120: the instructions there decode only the values 1, 2, 3, 4, 7, 13, 14, 15, 46, 47, 48, 49 and 50 — value 48 is printed as Selection F-DI for PROFIsafe (p10050, p10150)
and value 13 names the signal sources as (p10006, p10022 ... p10026). The G120 manual also expands: F-DI — Failsafe Digital Input, SLS — Safely-Limited Speed, SS1 — Safe Stop 1, STO — Safe Torque Off.
Parameters the manual names
- r9749 — SI message value: on S120/S150 and G130/G150 this is where the message value of C01712 is read (interpret decimal) to identify the cross-compared data.
- r2124 — alarm value: on G120 the message value of this message is read here.
- p9500 — SI Motion monitoring clock cycle (Control Unit): check it for equality with p9300 as part of the remedy for this message (S120/S150 and G130/G150 manuals).
- p9300 — SI Motion monitoring clock cycle (Motor Module): the counterpart to p9500; both must be equal.
Acknowledging and restarting
This safety message is accompanied by STOP F — while the discrepancy between the two monitoring channels exists, safe operation is no longer possible. For acknowledgment, the manuals for S120/S150 and G130/G150 describe a safe acknowledgment that works without a POWER ON: via the onboard F-DI (only CU310-2), via PROFIsafe, or from the machine control panel. The G120 manual notes that the message can be acknowledged via F-DI or PROFIsafe. The corrective work itself — parameterization checked and corrected, SI data copied to the second channel (on G120: to processor 2) with an acceptance test, and equal monitoring clock cycles in p9500 and p9300 — is listed under the checks above.
What differs between the drive families
Straight from the manuals' own fields — C01712 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | Control Unit (CU) | SINAMICS S120, S150 List Manual · p. 2693 |
| G130, G150 | NONE | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | Control Unit (CU) | SINAMICS G130, G150 List Manual · p. 1473 |
| G120 | — | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | — | SINAMICS G120 · p. 856 |
The drives this code lives on
C01712 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does message C01712 on a SINAMICS drive mean?
The SI Motion safety monitoring in the Control Unit found a difference between parameters or results of the F-IO processing when cross checking its two channels and initiated STOP F. One monitoring function no longer works reliably, so safe operation is no longer possible.
How do I fix C01712?
Correct the parameterization of the SI parameters named by the message value, copy the SI data to the second channel (on G120: to processor 2) and carry out an acceptance test. The S120/S150 and G130/G150 manuals also require equal monitoring clock cycles in p9500 and p9300.
Can C01712 be acknowledged without a POWER ON?
Yes. The manuals list safe acknowledgment via the onboard F-DI (only CU310-2), via PROFIsafe or from the machine control panel; on G120 the note names F-DI or PROFIsafe.
Where is the C01712 message value and what does it tell me?
In r9749 (S120/S150 and G130/G150) or r2124 (G120), interpreted decimal. The number identifies the cross-compared data — for example 3 for the SI STO input terminal (p10022, p10122) or 46 for the digital inputs debounce time (p10017, p10117).
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.