Safety message · SINAMICS G120, G130, G150, S120, S150

C01701SI Motion P1 (CU): STOP B initiated

What it means

C01701 “SI Motion P1 (CU): STOP B initiated” is a safety message of the Safety Integrated (SI) Motion monitoring in the CU: the drive is brought to a standstill with a STOP B, braking along the OFF3 deceleration ramp. The message also announces the next stage of the stop — as a result of this fault, message C01700 “STOP A initiated” is output once the time parameterized in p9556 has expired or the speed threshold parameterized in p9560 has been undershot; on the G120, C01700 follows once the speed threshold parameterized in p9560 is fallen below.

Why it appears

  • A stop request from the second monitoring channel — the G120 manual words this as a stop request from processor 2.
  • A subsequent response to C01714 “SI Motion CU: Safely-Limited Speed exceeded”.
  • A subsequent response to C01711 “SI Motion CU: Defect in a monitoring channel”.
  • A subsequent response to C01707 “SI Motion CU: tolerance for safe operating stop exceeded”.
  • A subsequent response to C01715 “SI Motion CU: Safely-Limited Position exceeded” or to C01716 “SI Motion CU: tolerance for safe motion direction exceeded” — the S120, S150, G130 and G150 manuals also list these two causes, which the G120 manual does not.

What to check

  1. Remove the cause of the fault on the second monitoring channel — on the G120, on the monitoring channel of processor 2.
  2. Carry out a diagnostics routine for C01714.
  3. Carry out a diagnostics routine for C01711.
  4. Carry out a diagnostics routine for C01707.
  5. On the S120, S150, G130 and G150, also carry out a diagnostics routine for C01715 and for C01716.

Parameters the manual names

  • p9556 — SI Motion STOP A delay time (Control Unit): during this STOP B, C01700 “STOP A initiated” is output once this delay time has expired; the S120, S150, G130 and G150 manuals name it for this message.
  • p9560 — SI Motion STO shutdown velocity (Control Unit): the speed threshold for this stop — C01700 “STOP A initiated” is output once the speed undershoots p9560; on the G120 this threshold alone determines when C01700 follows.

Acknowledging and restarting

The manuals describe how this message can be acknowledged without a POWER ON (safe acknowledgment): via the Terminal Module 54F (TM54F), the onboard F-DI (only CU310-2), PROFIsafe or the machine control panel. On the G120, the message is acknowledged without a POWER ON using “Acknowledge internal event”. Remove the cause of the fault before the drive is restarted.

What differs between the drive families

Straight from the manuals' own fields — C01701 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONE (OFF3)IMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS S120, S150 List Manual · p. 2675
G130, G150NONE (OFF3)IMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS G130, G150 List Manual · p. 1463
G120NONE (OFF3)IMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)SINAMICS G120 · p. 852

The drives this code lives on

C01701 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does C01701 in a SINAMICS drive mean?

The Safety Integrated (SI) Motion monitoring has stopped the drive with a STOP B, braking it along the OFF3 deceleration ramp. As a result of this fault, C01700 “STOP A initiated” follows once the p9556 delay has expired or the speed has undershot p9560.

Why did my drive report C01701?

Either the second monitoring channel issued a stop request (processor 2 on the G120), or the message is the follow-on reaction to C01714, C01711 or C01707 — on the S120, S150, G130 and G150 also to C01715 or C01716.

How can C01701 be acknowledged without a POWER ON?

Via a safe acknowledgment route: Terminal Module 54F (TM54F), onboard F-DI (only CU310-2), PROFIsafe or the machine control panel. On the G120, acknowledge the message using “Acknowledge internal event”.

Which parameters belong to C01701?

p9556, the SI Motion STOP A delay time, and p9560, the SI Motion STO shutdown velocity used here as the speed threshold. C01700 “STOP A initiated” is output when the p9556 time expires or the speed undershoots p9560.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.