Alarm · SINAMICS G130, G150, S120, S150

A33422Encoder 3: Pulses per revolution square-wave encoder outside tolerance bandwidth

What it means

Encoder 3, a square-wave encoder, is monitored for the distance between its zero marks. Alarm A33422 comes up when the measured zero mark distance no longer corresponds to the parameterized zero mark distance — the pulses per revolution of the square-wave encoder are then outside the tolerance bandwidth. The drive only raises the alarm when square-wave encoder PPR correction is active and fault 31131 has been re-parameterized, and the accumulator contains larger values than the tolerance thresholds p4683 or p4684. For a rotary encoder, the zero mark distance used for zero mark monitoring is set in p0425. Depending on the drive configuration, the same condition can also be output as a fault or as a message without a reaction.

Why it appears

  • The measured zero mark distance does not correspond to the parameterized zero mark distance.
  • With active square-wave encoder PPR correction and re-parameterized fault 31131, the accumulator contains larger values than p4683 or p4684.

What to check

  1. Check that the encoder cables are routed in compliance with EMC.
  2. Check the plug connections.
  3. Check the encoder type — it must be an encoder with equidistant zero marks.
  4. Adapt the parameter for the distance between zero marks (p0424, p0425).
  5. Replace the encoder or the encoder cable.

Reading the message value

  • The drive stores the alarm value in r2124; interpret the value as a decimal number.
  • It contains the accumulated differential pulses in encoder pulses.

Parameters the manual names

  • p0425 (Encoder rotary zero mark distance, Enc rot dist ZM) — sets the zero mark distance for zero mark monitoring of a rotary encoder; adapt it here when the measured distance does not match.
  • p0424 (Encoder linear zero mark distance, Enc lin ZM_dist) — the linear counterpart; the manual names p0424 and p0425 together for adapting the distance between zero marks.
  • p4683 (Zero mark monitoring tolerance window alarm threshold positive, ZM tol A_thr pos) — positive threshold of the tolerance window; the alarm triggers when the accumulator contains larger values.
  • p4684 (Zero mark monitoring tolerance window alarm threshold negative, ZM tol A_thr neg) — negative threshold of the tolerance window, complementing p4683.
  • r2124 (Alarm value) — read the accumulated differential pulses here, interpreted as a decimal value, to see the deviation in encoder pulses.

Acknowledging and restarting

As an alarm, A33422 requires no acknowledgement and the drive performs no automatic reaction while it is active. If the drive configuration outputs the same condition as a fault instead, the message must be acknowledged IMMEDIATELY.

The same on every family

Every manual that describes A33422 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEActual position/speed value incorrect or not available (11)Encoder 3SINAMICS S120, S150 List Manual · p. 3158
G130, G150NONENONEActual position/speed value incorrect or not available (11)Encoder 3SINAMICS G130, G150 List Manual · p. 1830

The drives this code lives on

A33422 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A33422 mean on a SINAMICS drive?

The measured zero mark distance of Encoder 3, a square-wave encoder, does not correspond to the parameterized zero mark distance. With active PPR correction and re-parameterized fault 31131, the accumulated differential pulses exceed the thresholds p4683 or p4684.

How do I clear A33422?

Check the EMC-compliant routing of the encoder cables and the plug connections, and verify that the encoder type has equidistant zero marks. Then adapt the zero mark distance in p0424 and p0425; if the deviation persists, replace the encoder or the encoder cable.

Does A33422 stop the drive?

No. As an alarm the drive performs no automatic reaction and no acknowledgement is needed; only when the configuration outputs the condition as a fault must it be acknowledged IMMEDIATELY.

Where can I see how large the deviation is?

In r2124, interpreted as a decimal value. It contains the accumulated differential pulses in encoder pulses.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.