Alarm · SINAMICS G130, G150, S120, S150

A08563PROFINET: Consistency error affecting adjustable parameters

What it means

The drive raises A08563 — PROFINET: Consistency error affecting adjustable parameters — when the configuration of the PROFINET interface is activated (p8925) and the consistency check detects an error in the adjustable parameters of that configuration. The alarm value identifies which item is inconsistent; it is stored in r2124 and must be interpreted decimal. Depending on the value, the conflict concerns the IP configuration, the station name, the combination of DHCP and an existing cyclic PROFINET connection, or a setting that clashes with the Industrial Ethernet interface (X127). For alarm values 0, 1, 2, 3, 4, 5 and 7 the configuration was not changed; for alarm value 6 the new configuration was nevertheless activated.

Why it appears

  • A consistency error was detected when the configuration for the PROFINET interface was activated (p8925) — the adjustable parameters do not form a consistent configuration.
  • Which item is inconsistent depends on the alarm value: the IP configuration (IP address, subnet mask or standard gateway), the station name, DHCP versus an existing cyclic PROFINET connection, or settings that conflict with the Industrial Ethernet interface (X127) — see the alarm value decoding below.

What to check

  1. Read the alarm value in r2124 (interpret decimal) and use the decoding below to determine which part of the configuration is inconsistent.
  2. Check the required interface configuration (p8940 and following) and correct it if necessary.
  3. Activate the corrected configuration (p8945).
  4. Alternatively, reinitialize the station using the "Edit Ethernet node" screen form (e.g. with STARTER).

Reading the message value

  • The drive enters the alarm value into the message value; it can be read in r2124 and is interpreted decimal. The values mean:
  • 0 — general consistency error
  • 1 — error in the IP configuration (IP address, subnet mask or standard gateway)
  • 2 — error in the station names
  • 3 — DHCP was not able to be activated, as a cyclic PROFINET connection already exists
  • 4 — a cyclic PROFINET connection is not possible as DHCP is activated
  • 5 — standard gateway is also set at the Industrial Ethernet interface (X127)
  • 6 — standard station name is also set at the Industrial Ethernet interface (X127)
  • 7 — IP address is located in the same subnet as the IP address of the Industrial Ethernet interface (X127)
  • For alarm values 0, 1, 2, 3, 4, 5 and 7 the configuration was not changed. For alarm value 6 the new configuration was nevertheless activated.
  • DHCP: Dynamic Host Configuration Protocol.

Parameters the manual names

  • r2124 (alarm value): read here, interpreted decimal, to identify which configuration item triggered the consistency error.
  • p8925 (Activate PN interface configuration): the activation during which the consistency error is detected.
  • p8940 (CBExx name of station) and the parameters that follow it: hold the required interface configuration to be checked and, if necessary, corrected.
  • p8945 (CBExx activate configuration of interfaces): activates the corrected interface configuration.
  • p8920 (PN name of station), p8921 (PN IP address), p8922 (PN Default Gateway) and p8923 (PN Subnet Mask): the PN settings the manual cross-references for this alarm — check the one the alarm value points to, e.g. the IP parameters for value 1 or the station name for values 2 and 6.

Acknowledging and restarting

No acknowledgement is required for this alarm. The condition is resolved by removing the inconsistency itself: check the required interface configuration (p8940 and following), correct it if necessary and activate it (p8945), or reinitialize the station using the "Edit Ethernet node" screen form (e.g. with STARTER). If the alarm value is 6, the new configuration was nevertheless activated — the conflict concerns the standard station name that is also set at the Industrial Ethernet interface (X127).

What differs between the drive families

Straight from the manuals' own fields — A08563 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2923
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1638

The drives this code lives on

A08563 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A08563 in SINAMICS mean?

The drive detected a consistency error while activating the configuration of its PROFINET interface (p8925): the adjustable parameters of that configuration contradict each other. The alarm value in r2124 shows which item is affected.

How do I fix alarm A08563?

Check the required interface configuration (p8940 and following), correct it if necessary and activate it with p8945, or reinitialize/reconfigure the station using the "Edit Ethernet node" screen form (e.g. with STARTER).

What does alarm value 6 of A08563 mean?

It means the standard station name is also set at the Industrial Ethernet interface (X127). Unlike alarm values 0, 1, 2, 3, 4, 5 and 7, the new configuration was nevertheless activated in this case.

Does A08563 need to be acknowledged?

No. The alarm is resolved by correcting the PROFINET interface configuration and activating it again (p8945) or by reconfiguring the station via the "Edit Ethernet node" screen form.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.