Alarm · SINAMICS G130, G150, S120, S150

A08562PROFINET: Syntax error in configuration file

What it means

The drive has detected a syntax error in the ASCII configuration file of its onboard PROFINET interface. Because of that error, the saved configuration file has not been loaded. The G130/G150 and S120/S150 manuals describe this alarm in identical words; it is a commissioning/parameterization error, not a hardware fault.

Why it appears

  • The ASCII configuration file for the onboard PROFINET interface contains a syntax error.
  • As a consequence of that error, the saved configuration file has not been loaded.

What to check

  1. Check the interface configuration held in p8920 and the parameters that follow it, and correct the syntax errors.
  2. Activate the corrected configuration with p8925 = 1.
  3. Save the parameters for the interface configuration, for example with p8925 = 2.

Alternatively, reinitialize the station using the "Edit Ethernet node" screen form, for example with the STARTER commissioning tool.

Parameters the manual names

  • p8920 (PN name of station) — the first of the parameters holding the onboard PROFINET interface configuration that has to be checked for the syntax error in this alarm.
  • p8925 (Activate PN interface configuration) — set to 1 to activate the corrected interface configuration, and to 2 to save the parameters for the interface configuration.

Acknowledging and restarting

No acknowledgement is required for this alarm. Once the syntax error has been corrected and the configuration activated (p8925 = 1), the cause is removed; the corrected configuration should then be saved (p8925 = 2).

The same on every family

Every manual that describes A08562 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2923
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1638

The drives this code lives on

A08562 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A08562 mean on a SINAMICS drive?

A syntax error has been found in the ASCII configuration file for the onboard PROFINET interface, so the saved configuration file has not been loaded.

How do I fix alarm A08562?

Check the interface configuration from p8920 onwards and correct the syntax errors, then activate the configuration with p8925 = 1 and save it with p8925 = 2. Alternatively, reinitialize the station via the "Edit Ethernet node" screen form, for example with STARTER.

Does A08562 have to be acknowledged?

No. No acknowledgement is required; once the corrected configuration has been activated with p8925 = 1, the cause of the alarm is removed.

Which parameters belong to alarm A08562?

p8920 and the parameters following it hold the PROFINET interface configuration to be checked, and p8925 activates the corrected configuration (value 1) or saves it (value 2).