Alarm · SINAMICS G130, G150, S120, S150

A08555Modbus TCP: commissioning error

What it means

A08555 is an alarm that reports an incorrect setting for the Modbus TCP protocol. The consequence of the incorrect setting is that Modbus is not activated — or, for the setting reported with alarm value 1, that CBE20 is not activated. Which setting the drive is complaining about is shown by the alarm value it writes to r2124. The manuals describe the alarm in the same way for the G130/G150 and the S120/S150.

Why it appears

The drive raises A08555 because the Modbus TCP protocol cannot be commissioned with the current settings:

  • Modbus is activated at the same time on the onboard interface (p2030) and on CBE20 (p8835), although CBE20 is not activated.
  • No drive object supported by Modbus is available under p0978[0], so Modbus is not activated.
  • The drive object SERVO with activated linear motor function (the FM bit LINMOT is set) is under p0978[0], so Modbus is not activated.

What to check

  1. Read the alarm value in r2124 (interpret it as a decimal number) to identify which setting is incorrect.
  2. For alarm value 1: check the parameterization of p2030 and p8835 and, if required, correct it.
  3. For alarm value 2, and for alarm value 3 on the S120/S150: appropriately resort the list of drive objects in p0978 so that a drive object supported by Modbus stands under p0978[0]. The manuals differ here in one point: on the S120/S150 Modbus supports the drive objects SERVO (without linear motor) and VECTOR, on the G130/G150 only VECTOR.

Reading the message value

The message value of the alarm is the alarm value, which the drive stores in r2124; interpret it as a decimal number:

  • 1 — Modbus is activated simultaneously on the onboard interface (p2030) and CBE20 (p8835), and CBE20 is not activated.
  • 2 — a drive object supported by Modbus is not available under p0978[0]; Modbus is not activated.
  • 3 — the drive object SERVO is under p0978[0] and the FM bit LINMOT is set; the manual words this same condition a second time as: the drive object SERVO with activated linear motor function is under p0978[0]. Modbus is not activated.

Parameters the manual names

  • r2124 — holds the alarm value of A08555; read it as a decimal number to see which Modbus TCP setting is wrong.
  • p2030 — field bus interface protocol selection: check here whether Modbus is activated on the onboard interface, and correct the setting for alarm value 1.
  • p8835 — CBE20 firmware selection: check whether Modbus is activated on the CBE20 and correct it together with p2030 for alarm value 1.
  • p0978 — list of drive objects: for alarm values 2 and 3, resort this list so that a drive object supported by Modbus stands under p0978[0].

Acknowledging and restarting

No acknowledgement is required for A08555. Correcting the setting is the remedy itself: once p2030 and p8835 (alarm value 1) or the drive object list p0978 (alarm values 2 and 3) have been corrected, no separate reset step is needed.

The same on every family

Every manual that describes A08555 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2922
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1637

The drives this code lives on

A08555 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A08555 mean on a SINAMICS drive?

It reports an incorrect setting for the Modbus TCP protocol as a commissioning error. The alarm value in r2124 shows which of the settings is wrong, and Modbus is consequently not activated (for alarm value 1, CBE20 is not activated).

How do I fix A08555?

For alarm value 1, check and if required correct p2030 and p8835. For alarm values 2 and 3, appropriately resort the drive object list in p0978 so that a drive object supported by Modbus stands under p0978[0].

Does A08555 have to be acknowledged?

No. The alarm requires no acknowledgement; correcting the incorrect Modbus TCP setting is sufficient.

Which drive objects does Modbus TCP support?

On the S120/S150 the protocol supports the drive objects SERVO (without linear motor) and VECTOR; on the G130/G150 only VECTOR. A SERVO drive object with activated linear motor function is not supported.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.