What it means
While evaluating the measuring probe that serves as encoder 3, the drive detected an error, so the evaluation cannot be carried out. Which of four possible errors occurred is stored as the alarm value in r2124 and must be read as a decimal number. Depending on how the drive is configured, the same condition can also be output as the fault F07579.
Why it appears
- An error occurred while the drive was evaluating the measuring probe on encoder 3; the alarm value in r2124 distinguishes which of the four possible triggers listed under fault value is present.
What to check
- Read the alarm value in r2124 as a decimal number; it identifies the trigger.
- Alarm value 6: assign the input terminal for the measuring probe in p0488, p0489 or p2517, p2518.
- Alarm value 4098: check the Control Unit hardware.
- Alarm value 4100: reduce the frequency of the measuring pulses arriving from the measuring probe.
- Alarm value 4200: set the ratio of the PROFIBUS clock cycle to the position controller clock cycle so that it is an integer multiple.
- If the evaluation is not needed on this drive, the manual gives a general remedy:
Deactivate the measuring probe evaluation (BI: p2509 = 0 signal)
.
Reading the message value
- The drive writes the alarm value to r2124; interpret it as a decimal number.
- 6 — the input terminal for the measuring probe has not been set.
- 4098 — initialization of the measuring probe failed.
- 4100 — the frequency of the measuring pulses is too high.
- 4200 — the PROFIBUS clock cycle is not an integer multiple of the position controller clock cycle.
Parameters the manual names
- r2124 — holds the alarm value of this message; read it as a decimal number to select the matching step in the checks.
- p2509 — BI: LR activate measuring probe evaluation; a 0 signal interconnected here switches the evaluation off, the manual's general remedy for this message.
- p0488 — measuring probe 1 input terminal; assign it here when the alarm value is 6.
- p0489 — measuring probe 2 input terminal; assign it here when the alarm value is 6.
- p2517 — LR direct measuring probe 1; alternative place to set the input terminal when the alarm value is 6.
- p2518 — LR direct measuring probe 2; alternative place to set the input terminal when the alarm value is 6.
Acknowledging and restarting
Remove the cause first; as an alarm, the message requires no acknowledgment. If the drive is configured to raise the condition as fault F07579 instead, the drive executes OFF1 and the fault is acknowledged IMMEDIATELY before the drive is restarted.
The same on every family
Every manual that describes A07579 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Application/technological function faulted (17) | None | SINAMICS S120, S150 List Manual · p. 2851 |
| G130, G150 | NONE | NONE | Application/technological function faulted (17) | None | SINAMICS G130, G150 List Manual · p. 1585 |
The drives this code lives on
A07579 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A07579 mean in SINAMICS?
The drive could not evaluate the measuring probe connected as encoder 3 because an error occurred during the evaluation. The alarm value in r2124, read as a decimal number, tells which of four errors occurred.
How do I fix A07579?
Apply the remedy matching the alarm value in r2124: set the input terminal in p0488, p0489, p2517 or p2518 for value 6, check the Control Unit hardware for 4098, reduce the measuring pulse frequency for 4100, or set the PROFIBUS clock cycle to an integer multiple of the position controller clock cycle for 4200. If the function is not needed, interconnect signal 0 at p2509.
Does A07579 have to be acknowledged?
As an alarm it needs no acknowledgment. Only when the drive outputs the condition as fault F07579 does it execute OFF1 and is an IMMEDIATE acknowledgment required.
Which parameters belong to A07579?
r2124 holds the alarm value, p2509 activates or deactivates the measuring probe evaluation, and p0488, p0489, p2517 and p2518 set the input terminals of the measuring probes.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the A07xxx group · SINAMICS manuals · Siemens manuals