Alarm · SINAMICS G130, G150, S120, S150

A07578Encoder 2: Measuring probe evaluation not possible

What it means

A07578 tells you that the drive could not evaluate the measuring probe connected at Encoder 2: an error occurred while the probe signal was being evaluated. Which error this is is reported in the alarm value, which the drive stores in r2124 — read it as a decimal number. Depending on how the drive is configured, the same condition can also appear as the fault F07578 instead of the alarm.

Why it appears

  • The drive detected an error while evaluating the measuring probe signal at Encoder 2.
  • The manual names four possible errors behind this message; which one applies is shown by the alarm value in r2124 (see the decoding below).

What to check

  1. Read the alarm value in r2124 as a decimal number; it tells you which of the four errors occurred.
  2. Alarm value 6: set the input terminal for the measuring probe — either in p0488 or p0489, or in the LR direct measuring probe inputs p2517 or p2518.
  3. Alarm value 4098: check the Control Unit hardware.
  4. Alarm value 4100: reduce the frequency at which the probe delivers its measuring pulses.
  5. Alarm value 4200: adjust the ratio so that the PROFIBUS clock cycle is an integer multiple of the position controller clock cycle.
  6. If the application does not need the probe, deactivate the measuring probe evaluation by applying signal 0 to p2509 — the message then goes away.

Reading the message value

  • 6 — no input terminal has been set for the measuring probe.
  • 4098 — initializing the measuring probe ended in an error.
  • 4100 — the frequency of the measuring pulses is too high.
  • 4200 — the PROFIBUS clock cycle is not an integer multiple of the position controller clock cycle.

Parameters the manual names

  • r2124 — holds the alarm value of this message; read it as a decimal number to pick the matching step.
  • p2509 — BI input that activates the measuring probe evaluation; signal 0 here switches the evaluation off.
  • p0488 — input terminal of measuring probe 1; used to assign the terminal when the alarm value is 6.
  • p0489 — input terminal of measuring probe 2; same use as p0488 for the second probe.
  • p2517 — LR direct measuring probe 1; alternative input to assign when the alarm value is 6.
  • p2518 — LR direct measuring probe 2; second LR direct probe input for the same purpose.

Acknowledging and restarting

As an alarm, A07578 does not trip the drive and needs no acknowledgment; it clears itself once the cause is removed and the probe evaluation runs again. Only when the drive is set up to output the condition as fault F07578 does it respond with OFF1, and that fault must be acknowledged immediately before the drive restarts.

What differs between the drive families

Straight from the manuals' own fields — A07578 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1584
S120, S150Application/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2850

The drives this code lives on

A07578 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07578 mean in SINAMICS?

The drive could not evaluate the measuring probe at Encoder 2 — an error occurred during the evaluation. The alarm value in r2124, read as a decimal number, shows which of the four possible errors applies.

How do I clear A07578?

Apply the measure for your alarm value: set the probe input terminal (p0488/p0489 or p2517/p2518), check the Control Unit hardware, reduce the measuring pulse frequency, or make the PROFIBUS clock cycle an integer multiple of the position controller clock cycle. If you do not need the probe, switch the evaluation off with signal 0 at p2509.

Does A07578 have to be acknowledged?

No — as an alarm it goes away by itself once the cause is removed. If it appears as fault F07578 instead, the drive goes to OFF1 and the fault must be acknowledged immediately.

What does alarm value 4200 in A07578 mean?

The PROFIBUS clock cycle is not an integer multiple of the position controller clock cycle. Set the clock cycle ratio between the two to an integer multiple.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A07xxx group · SINAMICS manuals · Siemens manuals