Alarm · SINAMICS G130, G150, S120, S150

A07577Encoder 1: Measuring probe evaluation not possible

What it means

A07577 appears on encoder 1 when the drive cannot evaluate the measuring probe signal: an error occurred while the probe was being evaluated. Depending on how the drive is configured, the same condition can also be issued as a fault instead of an alarm. The alarm value stored in r2124 states which of four possible errors is present.

Why it appears

  • An error occurred while the drive was evaluating the measuring probe on encoder 1; the alarm value in r2124 identifies which of the four problems below exists.
  • Alarm value 6: no input terminal has been assigned for the measuring probe.
  • Alarm value 4098: initialization of the measuring probe failed.
  • Alarm value 4100: the frequency of the measuring pulses is too high.
  • Alarm value 4200: the PROFIBUS clock cycle is not an integer multiple of the position controller clock cycle.

What to check

  1. Read the alarm value in r2124 as a decimal number; it tells you which of the four errors is present.
  2. If the measuring probe evaluation is not needed, switch it off by applying signal 0 to BI p2509 — this resolves the condition regardless of the alarm value.
  3. Alarm value 6: assign the input terminal for the measuring probe, either in p0488 and p0489 or in p2517 and p2518.
  4. Alarm value 4098: inspect the Control Unit hardware.
  5. Alarm value 4100: lower the frequency of the pulses delivered by the measuring probe.
  6. Alarm value 4200: change the clock cycle configuration so that the PROFIBUS clock cycle is an integer multiple of the position controller clock cycle.

Reading the message value

  • The drive writes the alarm value into r2124; interpret it as a decimal number.
  • 6 — probe input terminal missing.
  • 4098 — probe initialization failed.
  • 4100 — probe pulse frequency too high.
  • 4200 — PROFIBUS/position controller clock cycle ratio wrong.

Parameters the manual names

  • r2124 — read the alarm value stored here as a decimal number to see which of the four errors tripped the alarm.
  • p2509 — a signal 0 at this BI input switches the measuring probe evaluation off, ending the condition when the probe is not needed.
  • p0488 — assigns the input terminal for measuring probe 1; the place to set it when alarm value 6 is shown.
  • p0489 — assigns the input terminal for measuring probe 2; the second terminal for alarm value 6.
  • p2517 — input for the LR direct measuring probe 1; an alternative way to assign the terminal for alarm value 6.
  • p2518 — input for the LR direct measuring probe 2; likewise an alternative for alarm value 6.

Acknowledging and restarting

As an alarm, A07577 clears itself once the cause no longer applies; no acknowledgment action is needed. If the drive configuration raises the same condition as a fault instead, the drive performs an OFF1 stop, and the fault must be acknowledged immediately before the drive can be restarted.

The same on every family

Every manual that describes A07577 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2850
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1584

The drives this code lives on

A07577 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07577 on a SINAMICS drive mean?

The drive cannot evaluate the signal of the measuring probe on encoder 1 — an error occurred during the evaluation. The alarm value in r2124 shows which of four possible errors is present.

How do I fix alarm A07577?

Match the alarm value in r2124 to the remedy: assign the probe input terminal (p0488, p0489 or p2517, p2518) for value 6, inspect the Control Unit hardware for 4098, lower the pulse frequency for 4100, or set an integer clock cycle ratio for 4200.

Which parameter switches off the measuring probe evaluation?

p2509. Applying signal 0 to this BI input deactivates the evaluation, and the alarm no longer occurs.

Does A07577 stop the drive?

Not as an alarm. If the drive is configured to output the same condition as a fault, it performs an OFF1 stop and the fault must be acknowledged immediately.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.