What it means
A07520 is an alarm that the drive raises when a motor changeover cannot be carried out. In this function the drive switches between motors through contactors, and one of the conditions for the changeover is not met. The G130/G150 and S120/S150 manuals describe the alarm with identical causes and remedies. The drive stores an alarm value in r2124; interpreted as a decimal number it shows which of three situations stopped the changeover (see the alarm value list below).
Why it appears
- Alarm value 1: the contactor for the presently active motor cannot be opened. With a synchronous motor this happens while the speed r0063 is greater than the speed at the start of field weakening p0348: as long as r0063 > p0348, the current in the motor does not decay in spite of the pulses being suppressed.
- Alarm value 2: the 'contactor opened' feedback signal was not detected within 1 s.
- Alarm value 3: the 'contactor closed' feedback signal was not detected within 1 s.
What to check
- Read the alarm value in r2124 and interpret it as a decimal number — it tells you which of the three situations applies.
- Alarm value 1 — reduce the speed:
Set the speed lower than the speed at the start of field weakening (r0063 < p0348).
- Alarm values 2 and 3 — check the feedback signals of the contactor involved: the 'contactor opened' signal for alarm value 2, the 'contactor closed' signal for alarm value 3.
Reading the message value
- The drive writes the alarm value into r2124 and it must be interpreted as a decimal number; this alarm value appears as the message value %1.
- 1 — the contactor for the presently active motor cannot be opened, because for a synchronous motor the speed r0063 is greater than the speed at the start of field weakening p0348; as long as r0063 > p0348, the current in the motor does not decay in spite of the pulses being suppressed.
- 2 — the 'contactor opened' feedback signal was not detected within 1 s.
- 3 — the 'contactor closed' feedback signal was not detected within 1 s.
Parameters the manual names
- r2124 — alarm value: read it as a decimal number to identify which of the three causes (1, 2 or 3) the drive has detected.
- r0063 — CO: Actual velocity smoothed: the smoothed actual speed that, at alarm value 1, is compared with p0348.
- p0348 — the speed at the start of field weakening: the threshold of alarm value 1; the changeover contactor cannot be opened while r0063 > p0348, and the remedy requires r0063 < p0348.
Acknowledging and restarting
A07520 does not trip the drive and requires no acknowledgement: the alarm clears by itself once the changeover can be completed again — at alarm value 1 when the speed has been set so that r0063 < p0348, at alarm values 2 and 3 when the contactor feedback signals are detected again. No restart is needed.
The same on every family
Every manual that describes A07520 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Application/technological function faulted (17) | None | SINAMICS S120, S150 List Manual · p. 2839 |
| G130, G150 | NONE | NONE | Application/technological function faulted (17) | None | SINAMICS G130, G150 List Manual · p. 1575 |
The drives this code lives on
A07520 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A07520 mean?
The motor cannot be changed over. The decimal alarm value in r2124 says why: 1 — the contactor of the presently active motor cannot open because r0063 is above the speed at the start of field weakening p0348; 2 — the 'contactor opened' feedback was not detected within 1 s; 3 — the 'contactor closed' feedback was not detected within 1 s.
How is A07520 acknowledged or reset?
No acknowledgement is required and the drive does not trip. The alarm clears itself as soon as the changeover is possible again — speed below p0348, or the contactor feedback signals present.
Why does A07520 appear with alarm value 1 on a synchronous motor?
While r0063 is greater than p0348, the motor current does not decay in spite of the pulses being suppressed, so the contactor of the active motor cannot be opened. Set the speed lower than the speed at the start of field weakening (r0063 < p0348).
What should I check for A07520 alarm values 2 and 3?
The feedback signals of the contactor involved: the 'contactor opened' signal for value 2 and the 'contactor closed' signal for value 3. Each signal must be detected within 1 s.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.