A01487Topology: Option slot component not inserted

What it means

A01487 is a topology alarm: the drive compares the actual topology (the hardware that is really connected) with the target topology (the project in the commissioning software) and has found that an option slot component expected by the project is not inserted. The message value names the component in the form Component: %1, to %2, %3, connection: %4. Which component is meant and where it belongs can be read from the alarm value in r2124; component class and connection number are described in F01375. Under Topology --> Topology view the commissioning software offers improved diagnostics capability where relevant, e.g. a setpoint/actual value comparison.

Why it appears

  • The topology comparison has detected that an option slot component present in the target topology is missing in the actual topology, i.e. the component has not been inserted at the connection where the project expects it.

What to check

  1. Insert the components involved at the right connection, so that the actual topology matches the project again.
  2. Alternatively, adapt the project/parameterizing in the commissioning software, so that the target topology matches the hardware actually connected.
  3. Check the 24 V supply voltage.
  4. Check the DRIVE-CLiQ cables for interruption and contact problems.
  5. Check that the component is working properly.

Reading the message value

  • The drive stores the alarm value in r2124; it must be interpreted hexadecimal, pattern ddccbbaa hex.
  • dd = connection number (%4)
  • cc = component number (%3)
  • bb = component class (%2)
  • aa = component number of the component that has not been inserted (%1)
  • The component is described in dd, cc and bb, i.e. at the location where the component has not been inserted. Component class and connection number are described in F01375.

Parameters the manual names

  • r2124 — alarm value; read it as a hexadecimal ddccbbaa value to identify the missing option slot component, its class and the connection where it belongs.

Acknowledging and restarting

No acknowledgment is required for this alarm. The remedy consists of inserting the component at the correct connection or adapting the project to the actual topology; once target and actual topology match again, no further reset action at the drive is needed.

The same on every family

Every manual that describes A01487 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1422
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2613

The drives this code lives on

A01487 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01487 mean on a SINAMICS drive?

It is a topology alarm: the topology comparison has detected that an option slot component expected by the project (target topology) is missing in the actual topology, i.e. it is not inserted where the project expects it.

How do I find out which component is missing for A01487?

Read the alarm value in r2124 as a hexadecimal ddccbbaa value: aa is the component number of the missing component, bb its component class and dd the connection number. Component class and connection number are described in F01375, and the Topology view in the commissioning software offers additional diagnostics.

Does A01487 have to be acknowledged?

No, this alarm requires no acknowledgment. It is resolved by inserting the component at the right connection or by adapting the project so that target and actual topology match.

Which hardware should I check for A01487?

The 24 V supply voltage, the DRIVE-CLiQ cables for interruption and contact problems, and whether the component itself is working properly.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A01xxx group · SINAMICS manuals · Siemens manuals