Alarm · SINAMICS G130, G150, S120, S150

A01481Topology: Line Module not connected

What it means

A01481 is raised by the drive's topology comparison when a component that is configured in the target topology is not found in the actual topology — the hardware that is really connected. The message appears under three titles that name the component concerned: a power unit, a Motor Module or a Line Module, depending on which drive object reports the difference. Depending on how the drive is configured, the same condition can also be output with no reaction.

Why it appears

  • The topology comparison has detected a power unit, a Motor Module or a Line Module that is missing in the actual topology with respect to the target topology; which of the three components applies is shown by the title of the message.

What to check

  1. Adapt the topologies: insert the components involved at the right connection (correct the actual topology), or adapt the project/parameterization in the commissioning tool (correct the target topology).
  2. Open Topology --> Topology view in the commissioning tool; where relevant it offers improved diagnostics capability (e.g. setpoint/actual value comparison).
  3. Check the 24 V supply voltage.
  4. Check the DRIVE-CLiQ cables for interruption and contact problems.
  5. Check that the component is working properly.

Reading the message value

  • The message value reads Component: %1, to %2, %3, connection: %4; the drive stores the alarm value in r2124, to be interpreted hexadecimal as ddccbbaa.
  • dd = connection number (%4)
  • cc = component number (%3)
  • bb = component class (%2)
  • aa = component number of the component that has not been inserted (%1)
  • The component that has not been inserted is described in dd, cc and bb; component class and connection number are described in F01375.

Parameters the manual names

  • r2124 — alarm value of this message; read it hexadecimal (ddccbbaa) to identify the connection number, the component class and the component that has not been inserted.

Acknowledging and restarting

This alarm requires no acknowledgement and the drive takes no automatic reaction to it. It is resolved by inserting the component at the right connection or by adapting the project so that actual and target topology agree again.

What differs between the drive families

Straight from the manuals' own fields — A01481 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2608
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2610
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1418
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1419
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1419
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2609

The drives this code lives on

A01481 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01481 on a SINAMICS drive mean?

The topology comparison has detected a power unit, Line Module or Motor Module that is configured in the target topology but missing in the actual topology. The alarm value in r2124 identifies which component has not been inserted and at which connection.

How do I fix A01481?

Insert the component concerned at the right connection, or adapt the project in the commissioning tool so that the target topology matches the actual one. Then check the 24 V supply voltage, the DRIVE-CLiQ cables and that the component is working properly.

How can I see which component is missing for A01481?

Read r2124 hexadecimal as ddccbbaa: aa is the component number of the component that has not been inserted, bb its component class, cc the component number and dd the connection number. Component class and connection number are described in F01375.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.