Alarm · SINAMICS G130, G150, S120, S150

A01483Topology: Terminal Module not connected

What it means

A01483 – Topology: Terminal Module not connected. The drive compares the hardware actually connected (actual topology) with the configured project (target topology). This alarm is raised when the topology comparison detects a Terminal Module that is missing in the actual topology with respect to the target topology — the project expects a Terminal Module that the drive cannot find at the expected connection. The message value names the component concerned: “Component: %1, to %2, %3, connection: %4”. For improved diagnostics (e.g. setpoint/actual value comparison) the commissioning tool offers, where relevant, “Topology --> Topology view”.

Why it appears

  • The topology comparison has detected a Terminal Module that is missing in the actual topology with respect to the target topology: the project expects the component, but it is not present in the connected hardware at the expected connection.
  • The components involved are therefore either not inserted at the right connection, or the project/parameterization does not match the hardware actually connected.

What to check

  1. Correct the topology: insert the components involved at the right connection (this corrects the actual topology), or adapt the project/parameterizing in the commissioning tool (this corrects the target topology).
  2. Check the 24 V supply voltage.
  3. Check the DRIVE-CLiQ cables for interruption and contact problems.
  4. Check that the component is working properly.

Reading the message value

  • The drive stores the alarm value in r2124; it must be interpreted hexadecimal as ddccbbaa hex.
  • dd = connection number (%4)
  • cc = component number (%3)
  • bb = component class (%2)
  • aa = component number of the component that has not been inserted (%1)
  • The component is described in dd, cc and bb, where the component has not been inserted. The component class and the connection number are described in F01375.

Parameters the manual names

  • r2124 (alarm value) — read it hexadecimal as ddccbbaa to identify the connection number, the component number, the component class and the component that has not been inserted for this Terminal Module alarm.

Acknowledging and restarting

No acknowledgement is required for this alarm. The remedy is to correct the topology itself — either insert the components involved at the right connection or adapt the project/parameterizing in the commissioning tool — as described under checks.

The same on every family

Every manual that describes A01483 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2611
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1420

The drives this code lives on

A01483 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01483 in SINAMICS mean?

The topology comparison has detected a Terminal Module that is missing in the actual topology with respect to the target topology — the project expects a Terminal Module that the drive cannot find at the expected connection.

How do I clear A01483 Topology: Terminal Module not connected?

Insert the components involved at the right connection to correct the actual topology, or adapt the project/parameterizing in the commissioning tool to correct the target topology. Then check the 24 V supply voltage, the DRIVE-CLiQ cables and the component itself.

Where is the alarm value of A01483 decoded?

In r2124, interpreted hexadecimal as ddccbbaa: dd is the connection number, cc the component number, bb the component class and aa the component number of the component that has not been inserted. Component class and connection number are described in F01375.

Does A01483 have to be acknowledged?

No acknowledgement is required. The remedy is correcting the topology itself — inserting the component at the right connection or adapting the target topology — not a reset.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A01xxx group · SINAMICS manuals · Siemens manuals