What it means
The drive continuously compares the actual topology (the hardware as it is currently connected) with the target topology (the project in the commissioning tool). A01484 is raised when this comparison finds a DRIVE-CLiQ Hub Module missing in the actual topology with respect to the target topology — in other words, the project expects a Hub Module that is not present where it should be. The message value and the alarm value identify the affected component and connection. The alarm concerns the drive as a whole rather than one particular drive object.
Why it appears
- The topology comparison has detected a DRIVE-CLiQ Hub Module that is configured in the target topology but is missing in the actual topology.
- In practice this means either the components involved — including the Hub Module — are not inserted at the connection the project expects, or the project/parameterization no longer matches the hardware actually connected.
What to check
- Decide which side is wrong and correct it: if the hardware layout is the intended one, insert the components involved at the right connection (correct the actual topology); if the hardware is meant to be different, adapt the project/parameterization in the commissioning tool (correct the target topology).
- Where relevant, use the improved diagnostics of the commissioning tool under
Topology --> Topology view
(e.g. setpoint/actual value comparison). - Check the 24 V supply voltage.
- Check DRIVE-CLiQ cables for interruption and contact problems.
- Check that the component is working properly.
Reading the message value
- Message value:
Component: %1, to %2, %3, connection: %4
— the drive names the component that has not been inserted (%1), the component it should be connected to (%2, %3) and the connection (%4). - Alarm value (r2124, interpret hexadecimal): ddccbbaa hex, decoded as:
- dd = connection number (%4)
- cc = component number (%3)
- bb = component class (%2)
- aa = component number of the component that has not been inserted (%1)
- The component is described in dd, cc and bb, where the component has not been inserted. Component class and connection number are described in F01375.
Parameters the manual names
- r2124 (alarm value): read the value of this alarm as a hexadecimal number ddccbbaa to identify the connection number (dd), the component number (cc), the component class (bb) and the component that has not been inserted (aa).
Acknowledging and restarting
This alarm requires no acknowledgement, and the drive does not change its operating state because of it. Once you have corrected the actual topology or adapted the target topology so that the comparison no longer detects a missing DRIVE-CLiQ Hub Module, the alarm condition is resolved.
What differs between the drive families
Straight from the manuals' own fields — A01484 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1421 |
| S120, S150 | — | — | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2611 |
The drives this code lives on
A01484 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A01484 mean on a SINAMICS drive?
The topology comparison has found a DRIVE-CLiQ Hub Module that is configured in the target topology (the project) but is missing in the actual topology (the hardware as connected). The alarm value tells you which component and which connection are affected.
How do I clear A01484?
Either insert the components involved at the right connection so the actual topology matches the project, or adapt the project/parameterization in the commissioning tool so the target topology matches the hardware. Then check the 24 V supply, the DRIVE-CLiQ cables and the component itself.
Does A01484 stop the drive or need an acknowledgement?
No. The drive takes no action on this alarm and no acknowledgement is required; you only need to resolve the topology discrepancy between project and hardware.
How do I find out which Hub Module is missing?
Read the alarm value in r2124 as hexadecimal ddccbbaa: dd is the connection number, cc the component number, bb the component class and aa the component that has not been inserted. Component classes and connection numbers are described in F01375.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.