Alarm · SINAMICS G130, G150, S120, S150

A01425Topology: Serial number different

What it means

A01425 is raised when the drive's topology comparison detects a difference between the actual topology and the target topology on one component: the serial number of the connected component is not the one expected. The message value names the affected component — %1 is the component number, %2 the component class — and %3 is the number of differences.

Although this is only an alarm, its effect is drastic: The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.

Why it appears

  • The topology comparison has detected a difference between the actual and the target topology in relation to one component: the serial number is different.

What to check

  1. Read the alarm value in r2124 and interpret it hexadecimal in the form ddccbbaa: byte aa is the component number (%1), byte bb the component class (%2) — the component classes are described in F01375 — and byte cc the number of differences (%3).
  2. Open "Topology --> Topology view" in the commissioning tool (commissioning software); where relevant it offers improved diagnostics capability, e.g. a setpoint/actual value comparison for the affected component.
  3. Adapt the topologies: either change over the actual topology so that it matches the target topology, or download the target topology that matches the actual topology using the commissioning tool.
  4. Acknowledge or deactivate the differences as byte cc requires: if cc = 1, acknowledge using p9904 or p9905; if cc > 1, acknowledge using p9905 and deactivate using p9906 or p9907/p9908.

Reading the message value

  • The drive stores the alarm value in r2124; it must be interpreted hexadecimal in the form ddccbbaa.
  • dd = reserved.
  • cc = number of differences (%3).
  • bb = component class (%2).
  • aa = component number (%1).

Parameters the manual names

  • r2124 — alarm value: read the hexadecimal value ddccbbaa here to identify the component (number and class) and the number of differences.
  • p9904 — topology comparison acknowledge differences: use it to acknowledge the difference when exactly one difference is present (cc = 1).
  • p9905 — device specialization: acknowledges the difference, both alone when cc = 1 and as the acknowledgement step when cc > 1.
  • p9906 — topology comparison, comparison stage of all components: use it to deactivate the differences when more than one difference is present (cc > 1).
  • p9907 — topology comparison, comparison stage of the component number: use it to deactivate the differences when cc > 1.
  • p9908 — topology comparison, comparison stage of a component: use it to deactivate the differences when cc > 1.

Acknowledging and restarting

The alarm is not removed by simply clearing it at the drive; the topology difference itself must be resolved and then acknowledged via the parameters: with one difference (byte cc = 1 in r2124) using p9904 or p9905; with more than one difference (cc > 1) using p9905, and deactivated with p9906 or p9907/p9908. As long as the alarm is present, the drive system is no longer booted and the closed-loop drive control cannot be enabled, so the drive only comes back once the topology matches and the difference has been acknowledged or deactivated.

The same on every family

Every manual that describes A01425 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1417
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2607

The drives this code lives on

A01425 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01425 mean on a SINAMICS drive?

The topology comparison has detected that, for one component, the serial number in the actual topology differs from the target topology. As a consequence, the drive system is no longer booted and the closed-loop drive control cannot be enabled.

How do I acknowledge or clear A01425?

First adapt the topologies — change over the actual topology to match the target topology, or download a matching target topology via the commissioning tool. Then acknowledge with p9904 or p9905 if there is one difference (cc = 1); with more than one difference, acknowledge with p9905 and deactivate using p9906 or p9907/p9908.

How can I find out which component triggered A01425?

Read the alarm value in r2124, interpreted hexadecimal as ddccbbaa: aa is the component number, bb the component class (described in F01375) and cc the number of differences. The commissioning tool's "Topology --> Topology view" additionally offers improved diagnostics such as a setpoint/actual value comparison.

Why does my drive not start while A01425 is active?

While the serial number difference is present, the drive system is no longer booted, so the drive control (closed-loop) cannot be enabled. The difference must first be resolved and acknowledged or deactivated via the topology comparison parameters.