Alarm · SINAMICS G120, G120XA, G130, G150, S120, S150

A01069Parameter backup and device incompatible

What it means

A01069 is raised when the parameter backup on the memory card does not match the drive unit in which the card is used. A typical case named in the manual: devices A and B are not compatible, and a memory card with the parameter backup for device A is inserted in device B. As a result, the module boots with the factory settings.

Why it appears

  • The parameter backup on the memory card and the drive unit do not match.
  • Example given by the manual: devices A and B are not compatible, and a memory card with the parameter backup for device A is inserted in device B.
  • Because of this mismatch, the module boots with the factory settings.

What to check

  1. Insert a memory card with a parameter backup that is compatible with this device and carry out a POWER ON.
  2. Alternatively, insert a memory card without a parameter backup and carry out a POWER ON.
  3. On G120 and G120XA the manual additionally allows: if required, withdraw the memory card and carry out POWER ON.
  4. Save the parameters afterwards. On G130, G150, S120 and S150 this is done with p0977 = 1; on G120 and G120XA with p0971 = 1.

Parameters the manual names

  • p0977 (Save all parameters): set to 1 to save all parameters after booting on G130, G150, S120 and S150 with a compatible card or a card without parameter backup.
  • p0971 (Save parameters): set to 1 to save the parameters after booting on G120 and G120XA with a compatible card or a card without parameter backup.

Acknowledging and restarting

No acknowledgement is required, and the drive takes no automatic reaction to this alarm. The condition is resolved by carrying out a POWER ON with a suitable memory card — one whose parameter backup matches the device, or one without parameter backup — and then saving the parameters as described above.

What differs between the drive families

Straight from the manuals' own fields — A01069 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)Control Unit (CU)SINAMICS G130, G150 List Manual · p. 1387
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)Control Unit (CU)SINAMICS S120, S150 List Manual · p. 2574
G120NONENONEError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 830
G120XANONENONESINAMICS G120XA PN converter · p. 1107

The drives this code lives on

A01069 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01069 on a SINAMICS drive mean?

The parameter backup on the memory card does not match the drive unit, so the module boots with the factory settings. This happens, for example, when a card written for one device is inserted into an incompatible device.

How do I clear A01069?

Insert a memory card with a compatible parameter backup, or one without a parameter backup, and carry out a POWER ON. Then save the parameters with p0977 = 1 on G130/G150 and S120/S150, or with p0971 = 1 on G120/G120XA.

Does A01069 have to be acknowledged?

No, the alarm requires no acknowledgement and the drive takes no automatic reaction. It is resolved by a POWER ON carried out with a suitable memory card, followed by saving the parameters.

Codes next to this one