YCAV0569, YCAV0639, YCAV0679, YCAV0719, YCAV0739, YCAV0819, YCAV0889, YCAV0969 Style A 50 Hz Installation, Operation and Maintenance

Document typeInstallation Guide
Document number201.21-NM2
EquipmentYCAV Variable Speed Drive Screw Chiller
BrandYORK
Revised2023-12-20
File size8.6 MB

Fault codes in this document

VSD SAFETIES (FAULTS)

Code / displayMeaningCauseActionPage
UNIT  YYYYYYYY
 PRECHARGE - LOW  DC  BUS  VOLTAGE

SYS  X  YYYYYYYY  PRECHARGE - LOW  DC  BUS VOLT
DC bus voltage failed to reach minimum levels during pre-charge intervalDC bus voltage did not reach at least 50 VDC within four seconds and 500 VDC within 19 seconds after the pre-charge signal was assertedAuto-restart safety. Locks out on 3rd fault in 90 minutes. Lockout requires manual reset using keypad.173
UNIT  YYYYYYYY
 PRECHARGE - DC  BUS  VOLTAGE  IMBALANCE

SYS  X  YYYYYYYY  PRECHARGE-BUS  VOLT IMBAL
Half-bus voltage deviated beyond tolerance during pre-charge intervalThe 1/2 DC bus voltage magnitude exceeded +/- 100 VDC of the total DC bus voltage divided by two during the pre-charge intervalLocks out on 1st fault. Will not restart until operator clears the fault using the keypad.173
UNIT  YYYYYYYY
 HIGH  DC  BUS  VOLTAGE

SYS  X  YYYYYYYY  HIGH  DC  BUS  VOLTAGE
DC bus voltage exceeded hardware trip levelDC bus exceeded 766 +/- 30 VDC hardware trip level on the VSD Logic BoardImmediate shutdown. Auto-restart safety. Locks out on 3rd fault in 90 minutes.173
UNIT  YYYYYYYY
 LOW  DC  BUS  VOLTAGE

SYS  X  YYYYYYYY  LOW  DC  BUS  VOLTAGE
DC bus voltage dropped below software trip levelDC bus dropped below 500 VDCImmediate shutdown. Auto-restart safety. Locks out on 3rd fault in 90 minutes.174
UNIT  YYYYYYYY
 DC  BUS  VOLTAGE  IMBALANCE

SYS  X  YYYYYYYY DC BUS  VOLTAGE  IMBALANCE
Half-bus voltage deviated beyond tolerance during operationThe 1/2 DC bus magnitude exceeded the +/- 100 VDC tolerances of the total DC bus voltage divided by twoImmediate shutdown. Locks out on 1st fault. Will not restart until operator clears the fault using the keypad.174
SYS  X  YYYYYYYY  HIGH  MOTOR  CURRENTInstantaneous peak motor current exceeded hardware limitNominal peak current trip level is 575.5 Amps (554A min., 597A max.). 380V AC, 60Hz and 400V AC, 50Hz nominal peak current trip level is 649.5 Amps (626 Amps min., 674 Amps max.)Immediate shutdown. Auto-restart safety. Locks out system on 3rd fault in 90 minutes.174
SYS  X  YYYYYYYY  MOTOR  CURRENT  OVERLOADHighest phase motor current exceeded overload setting continuously for 20 secondsHighest of the 3 phases of motor current per compressor exceeded the compressor's 105% FLA ADJUST potentiometer setting on the VSD Logic Board continuously for 20 secondsControlled ramped shutdown. Locks out system on 1st fault. Will not restart until operator clears the fault using the keypad.175
UNIT  YYYYYYYY
  MOTOR  CURRENT  OVERLOAD
Highest phase motor current exceeded overload setting continuously for 30 seconds across all compressorsHighest of the 3 phases of motor current per compressor exceeded the compressor's overload ADJUST potentiometer setting continuously for 30 secondsImmediate shutdown. Locks out all systems on 1st fault. Will not restart until operator clears the fault using the keypad.175
SYS  X  YYYYYYYY  GATE  DRIVERIGBT short circuit detected or gate driver power supply lowIGBT saturation voltage (VCE SAT) exceeded prescribed limit due to short circuit condition, or IGBT Gate Driver board power supply voltage fell below permissible limitImmediate shutdown. Auto-restart safety. Locks out on 3rd fault in 90 minutes.175
SYS X YYYYYYYY  HIGH  VSD  BASEPLATE  TEMPIGBT baseplate temperature exceeded software trip pointBaseplate temperature exceeded limit — 218°F for 2 and 4 compressor chillers, 232°F for 3 compressor chillersControlled ramped shutdown. Auto-restart safety. Locks out on 3rd fault in 90 minutes. Fans and water pump remain energized until baseplate temperature falls below 165°F; restart allowed when temperature drops below this value.176
UNIT  YYYYYYYY
 HIGH  VSD  INTERNAL  AMBIENT  TEMP
VSD internal cabinet ambient temperature rose above cutoutVSD internal ambient temperature rose above the cutout of 158°FControlled ramped shutdown. Does not cause lockout. Restarts when internal ambient temperature drops 10°F below the cutout (148°F).176
UNIT  YYYYYYYY
 SINGLE  PHASE  INPUT  VOLTAGE

SYS X YYYYYYYY SINGLE PHASE INPUT VOLTS
One of three input line voltages missingSCR Trigger Control board circuitry detected absence of any of the three-phase line voltagesImmediate shutdown. Does not cause lockout. Restarts when the single phase condition clears.176
UNIT  YYYYYYYY
 VSD  LOGIC  BOARD  POWER  SUPPLY
One or more DC power supplies to VSD Logic Board outside allowable limitsMonitored DC power supplies on the VSD Logic Board fell outside their allowable limitsImmediate shutdown. Auto-restart safety. Restarts after fault clears. Locks out on 3rd fault in 90 minutes.177
SYS  X  YYYYYYYY  VSD  RUN  RELAYHardware and software run signals did not match within 5-second windowMissing run signal not asserted within the 5-second window, or remaining run signal not disabled within 5 seconds after the VSD was shut downControlled ramped shutdown if running. Auto-restart safety. Autostarts after 120 second anti-recycle timer times out. Locks out on 3rd fault in 90 minutes.177
UNIT  YYYYYYYY
 VSD  LOGIC  BOARD  FAILURE
PWM generator did not acknowledge voltage and frequency commandsSystem microprocessor did not receive handshake from PWM generator within 1.5 seconds of issuing the commandAll systems immediately shut down. Auto-restart safety. Auto restarts after 120 second anti-recycle timer. Locks out on 3rd fault in 90 minutes.177
UNIT  YYYYYYYY
 VSD  CT  PLUG FAULT
CT plug not installed on VSD Logic BoardJumper in CT plug not installed, causing a low value read on the digital inputImmediate shutdown or prevented from running. Auto-restart safety. Restarts after 120 second anti-recycle timer. Locks out on 3rd fault in 90 minutes.177

UNIT WARNINGS

Code / displayMeaningCauseActionPage
UNIT WARNING:  !!  LOW BATTERY  !!
 CHECK  SETPOINTS/PROGRAM/OPTIONS/TIME
RTC battery voltage low at power-upRTC battery determined to be low at micropanel power-upAll programmed setpoints, program values, time, schedule, and history buffers lost and reset to defaults. Unit prevented from running until MANUAL OVERRIDE key pressed. Anti-recycle timers set to default to allow time to check settings. Replace battery as soon as possible.180
UNIT  WARNING:
 INVALID NUMBER OF COMPRESSSORS SELECTED
No or multiple "Number of Compressors Select" jumpers installedNo jumpers installed or more than 1 jumper installed in the VSD wiring harness at power-upTurn off both control panel and VSD control voltage. Install proper jumpers in the VSD wiring harness (see Page 136).183
UNIT  WARNING:  INVALID  SERIAL  NUMBER
 ENTER UNIT  SERIAL  NUMBER
Chiller serial number not programmed or lostChiller Control Board replaced, EPROM changed, or factory programming lostContact YORK Product Technical Support immediately. Serial number entered using Service Key with factory password. Optimized IPLV chiller will only run in Standard IPLV mode until serial number is programmed.183
UNIT WARNING:  OPTIMIZED  EFFICIENCY
 DISABLED - CONTACT  YORK  REPRESENATIVE
Optimized chiller programmed for standard controlHigh IPLV mode not enabled — serial number not programmed or option not activatedContact YORK Product Technical Support or YORK ES Commercial. Special password required to enable optimized IPLV control via Service Key.183

UNIT SAFETIES

Code / displayMeaningCauseActionPage
UNIT YYYYYYYY
 LOW AMBIENT TEMP
Ambient temperature below programmable low ambient cutoutAmbient temperature fell below the programmable Low Ambient Temp Cutout (only if enabled under OPTIONS key)Controlled ramped shutdown. Auto-restart when temperature rises 2°F above cutout. Cannot cause lockout. Unit inhibited from starting when temperature below cutout + 2°F.184
UNIT  YYYYYYYY
LOW  LEAVING  CHILLED  LIQUID  TEMP
Leaving chilled liquid temperature below freeze protection cutoutLeaving chilled liquid temperature dropped below the programmable cutout point (low flow conditions or improperly programmed setpoint values)Controlled ramped shutdown. Auto-restart when chilled liquid temperature rises 4°F above cutout. Cannot cause lockout. Unit inhibited from starting when temperature below cutout + 4°F.185
UNIT  YYYYYYY
VSD  COMMUNICATIONS  FAILURE
Chiller Control Board lost or never established communications with VSD Logic BoardNo valid response received for 8 seconds during operation, or initialization data not received at power-upControlled ramped shutdown. Unit inhibited from starting until communications established. Automatically resets when Chiller Control Board receives a valid response from the VSD.185

SYSTEM SAFETIES (FAULTS)

Code / displayMeaningCauseActionPage
SYS  X  YYYYYYYY  HIGH  DISCHARGE  PRESSUREDischarge pressure rose above software cutout thresholdDischarge pressure rose above 274 PSIG for 0.5 secondsControlled ramped shutdown. Restart allowed when discharge pressure falls to 259 PSIG. Inhibited from starting if pressure above 259 PSIG. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.186
SYS  X  YYYYYY  HPCO  FAULTMechanical high pressure cutout contacts openedMechanical high pressure cutout opened at 297+/-8 PSIGImmediate shutdown. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes. HPCO resets (closes) at 230+/-10 PSIG.187
SYS  X  YYYYYYYY  LOW  SUCTION  PRESSURESuction pressure fell below programmable cutoutSuction pressure fell below the programmable cutout (typically 24 PSIG for chilled water applications); low refrigerant charge or low flowControlled ramped shutdown. Cutout ignored for first 30 seconds of run time; linearly ramped from 10% of cutout up to full value over next 3 minutes. Transient override provides additional 30-second grace period after 3.5 minutes. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.187
SYS  X  YYYYYYYY  LOW  MOTOR  CURRENTAbsence of motor current detected (<10%FLA)Microprocessor detected motor current below 10%FLA, usually indicating compressor is not runningControlled ramped shutdown. Safety ignored for first 10 seconds of operation. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.187
SYS  X  YYYYYYYY  HIGH  DIFF  OIL  PRESSUREDischarge-to-oil differential pressure rose above cutoutDischarge to Oil Differential Pressure rose above the cutout of 65 PSID (possibly dirty oil filter)Controlled ramped shutdown. Safety ignored for first 90 seconds of run time. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.188
SYS  X  YYYYYYYY  LOW  DIFF  OIL  PRESSUREOil-to-suction differential pressure fell below cutoutDifferential between oil and suction pressure fell below the cutout (compressor not pumping sufficiently to push oil through lubrication system)Controlled ramped shutdown. Safety ignored for first 60 seconds; cutout linearly ramped from 0 PSID to 30 PSID over 5–10 minutes based on ambient temperature. 30-second bypass below 50 Hz during rampdown. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.188
SYS  X  YYYYYYYY  HIGH  DSCHARGE  TEMPDischarge temperature rose above cutoutDischarge temperature rose above 250°FControlled ramped shutdown. Inhibited from starting if discharge temperature above 200°F. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.188
SYS  X  YYYYYYYY  HIGH  OIL  TEMPOil temperature rose above cutoutOil temperature rose above 225°FControlled ramped shutdown. Inhibited from starting if oil temperature above 175°F. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.189
SYS  X  YYYYYYYY  LOW  SUCTION  SUPERHEATSuction superheat fell below threshold indicating liquid floodback riskOne of: suction superheat <2.0°F with discharge superheat <15°F (run time <5 min, ramped cutout over 60 sec); suction superheat <2°F with discharge superheat <15°F for 10 sec (run time ≥5 min); suction superheat <0.5°F with discharge superheat >15°F for 60 sec (run time ≥5 min); suction superheat <5°F for 10 minutesControlled ramped shutdown. Ignored for first 30 seconds of operation. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.189
SYS  X  YYYYYYYY  LOW  DISCHARGE  SUPERHEATDischarge superheat fell below threshold indicating liquid floodback through economizerAfter first 5 minutes of run time, discharge superheat fell below 10.0°F for 5 minutesControlled ramped shutdown. Ignored for first 5 minutes of operation. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.189
SYS  X  YYYYYYYY  SENSOR  FAILURE:
ZZZZZZZZZZZZ
Critical sensor reading out of range or not functioning properlyCritical sensor (transducer, level sensor, or motor winding temp sensor) reading out of range high or low. Possible values: SUCT PRESS, OIL PRESS, DSCH PRESS, LEVEL SENSOR, MOTOR TEMP XPrevents system from running at start-up; faults and shuts down system while in operation if threshold exceeded. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.190
SYS X  YYYYYYYY  HIGH  MOTOR  TEMPCompressor motor temperature too highAny compressor motor temperature sensor rose above 250°FControlled ramped shutdown. Inhibited from starting if motor temperatures above 240°F. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.190
SYS  X  YYYYYYYY  HIGH  FLASH TANK  LEVELLiquid level in flash tank too highTank level greater than 85% for 10 secondsControlled ramped shutdown. Safety ignored for first 15 seconds of operation. Auto-restart after 120 second anti-recycle timer. Locks out after 3 faults in 90 minutes.191
SYS  X  YYYYYYYY  CONTROL  VOLTAGE115VAC control voltage to one system missingSystem fuse removed or blown, causing loss of 115VAC supply to the affected systemImmediate shutdown of affected system. Does not cause lockout. Resets automatically when power is returned.191