Safety shutdown · YORK YCAV · Variable speed drive screw chiller

YORK YCAVUNIT VSD LOGIC BOARD FAILURE

On the display

The panel prints UNIT YYYYYYYY VSD LOGIC BOARD FAILURE. The characters the manual shows as YYYYYYYY, standing between "UNIT" and "VSD LOGIC BOARD FAILURE", indicate a FAULT condition, which restarts, or a LOCKOUT. All listings of this safety in the manuals use this single wording, and the message is one of the unit's VSD safeties (faults).

What it means

This is a software-generated VSD safety. When the control issues voltage and frequency commands, the PWM generator must acknowledge receipt of the command; the fault means the system microprocessor did not receive that handshake within 1.5 seconds of issuing the command, and the unit trips. It is a unit fault for all units: if it occurs while the chiller is running, all systems shut down immediately. The safety is only active during precharge and during running of a compressor — it is not active when all compressors are shut down and the precharge is disabled.

Why it appears

  • The PWM generator does not acknowledge the voltage and frequency commands within 1.5 seconds of issue, so the system microprocessor receives no handshake and the unit trips.

Setpoints and thresholds

  • Handshake window: the PWM generator must acknowledge the voltage and frequency commands within 1.5 seconds of issue.
  • Active window: during precharge and while a compressor is running.
  • Auto-restart timer: 120-second anti-recycle timer.
  • Lockout threshold: 3rd fault within 90 minutes.

Reset and restart

This is an auto-restart safety: after a trip, the unit restarts by itself once the 120-second anti-recycle timer times out. If the fault recurs, it locks out on the 3rd fault in 90 minutes. A lockout is not cleared by the auto-restart — On lockout, cleared using the keypad.

Questions engineers ask

What does UNIT VSD LOGIC BOARD FAILURE mean on a York YCAV?

It is a software-generated VSD safety: the PWM generator did not acknowledge the voltage and frequency commands within 1.5 seconds of issue, so the system microprocessor trips the unit.

Why did all systems shut down when this message appeared?

It is a unit fault for all units. The safety is active during precharge and while a compressor is running, so if it trips while the chiller is running, all systems shut down immediately.

Does the YCAV restart by itself after this trip?

Yes. It is an auto-restart safety and restarts after the 120-second anti-recycle timer times out, but it locks out on the 3rd fault in 90 minutes.

How do I clear a UNIT VSD LOGIC BOARD FAILURE lockout?

A lockout is not cleared by the auto-restart; the manual states it is cleared using the keypad.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YCAV; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: