On the display
The panel shows SYS X LOW SUCTION PRESSURE on the system display; X is the system number. The manual prints the full line as SYS X YYYYYYYY LOW SUCTION PRESSURE
, where YYYYYYY indicates a "FAULT" condition or "LOCKOUT" — so the message tells you both what tripped and whether the system is merely in fault or locked out.
What it means
This is a software safety that triggers a controlled ramped shutdown of the system: the control has detected that suction pressure fell below the programmable cutout. It is the programmable secondary back-up for the flow switch — it protects against operation with low refrigerant charge and helps protect the chiller from evaporator freeze-up. Because it is a software function with staged timing (below), it does not trip on the first instant of low pressure after a start.
Why it appears
- Suction pressure falls below the programmable cutout — typically set at 24 PSIG for chilled water applications.
- Low refrigerant charge.
- Low flow.
What to check
- Check the refrigerant charge — the safety exists specifically to protect against operation with a low charge.
- Check for low flow — low flow is listed as a cause, and this cutout serves as the secondary back-up for the flow switch.
Setpoints and thresholds
- Cutout point: programmable; typically set at 24 PSIG for chilled water applications.
- First 30 seconds of run time: the cutout is ignored.
- Next 3 minutes of run time: the cutout point ramps linearly from 10% of the cutout value up to the programmed cutout.
- After the first 3 minutes 30 seconds (3.5 minutes) of run time: a transient sets a 30-second timer with a linearly ramped cutout starting at 10% of the programmed cutout — if the suction pressure does not stay above the ramped cutout over those 30 seconds, the system faults.
- The manual gives the ramp as
Cutout = ((Programmed Cutout x Run Time) / 200) - 1.2 PSIG
Reset and restart
The shutdown itself is a controlled ramped shutdown with no manual action needed in the ordinary case: the system auto-restarts once the 120-second anti-recycle timer times out. It locks out after 3 faults on the same system within 90 minutes. On LOCKOUT the system will not restart until the operator clears the fault using the keypad; the manual also gives the lockout clear action as cycling the system switch OFF and ON
.
Questions engineers ask
What does SYS X LOW SUCTION PRESSURE mean on a YORK YCAV?
It is a software safety meaning suction pressure fell below the programmable cutout (typically 24 PSIG for chilled water applications). It is the secondary back-up for the flow switch and produces a controlled ramped shutdown.
What causes the low suction pressure trip?
The manual lists suction pressure below the programmable cutout, with low refrigerant charge or low flow as the underlying causes. The cutout serves to protect against low charge operation and evaporator freeze-up.
Will the YCAV restart by itself after this trip?
Yes — it auto-restarts after the 120-second anti-recycle timer times out. The exception is a lockout, which occurs after 3 faults on the same system within 90 minutes.
How do I clear the LOCKOUT for this message?
On LOCKOUT the system will not restart until the operator clears the fault using the keypad. The manual also states the lockout is cleared by cycling the system switch OFF and ON.
Messages next to this one
The same message on other models
Source
Written from the manufacturer's manuals for the YORK YCAV; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All YORK YCAV messages: fault codes · YORK YCAV documentation · YORK manuals