Safety shutdown · YORK YCAV · Variable speed drive screw chiller

YORK YCAVSYS X HIGH DISCHARGE PRESSURE

On the display

The panel shows the fault as SYS X YYYYYYYY HIGH DISCHARGE PRESSURE in the system safeties (faults) group. X is the number of the affected system, and YYYYYYYY is the status word printed in its place: FAULT for a condition that restarts automatically, or LOCKOUT. The manual calls this the High Discharge Pressure Cutout (Software) Fault.

What it means

A software system safety has tripped on the affected system: the discharge pressure rose above 274 PSIG for 0.5 seconds, and the system shuts down with a controlled ramped shutdown. The status word in the message tells you where things stand — FAULT means the system may restart by itself once conditions allow, LOCKOUT means the system has locked out on this fault and stays off until it is reset manually.

Why it appears

  • The discharge pressure rises above the 274 PSIG software cutout threshold and stays there for 0.5 seconds — this is the trip condition the manuals give as the cause; no other cause is listed for this safety.

Setpoints and thresholds

  • Trip threshold: discharge pressure above 274 PSIG for 0.5 seconds.
  • Restart and start-inhibit threshold: 259 PSIG — the system may restart when the pressure falls to 259 PSIG, and it is inhibited from starting while the pressure is above 259 PSIG.
  • Anti-recycle timer: 120 seconds before an automatic restart takes place.
  • Lockout count: any 3 faults on the same system within 90 minutes lock the system out on the last fault.

Reset and restart

A FAULT clears itself: once the discharge pressure falls to 259 PSIG, the system restarts automatically when the 120-second anti-recycle timer times out. After 3 faults on the same system within 90 minutes, the system locks out on the last fault and needs a manual reset — a lockout requires a manual reset by cycling the respective system switch OFF and ON. One of the manuals adds that on lockout the system will not restart until the operator clears the fault using the keypad.

Questions engineers ask

What does SYS X HIGH DISCHARGE PRESSURE mean on a YORK YCAV?

It is a software system safety: the discharge pressure rose above 274 PSIG for 0.5 seconds and the system shuts down with a controlled ramped shutdown. X is the number of the affected system, and the status word shows FAULT (auto-restart) or LOCKOUT.

How do I clear a HIGH DISCHARGE PRESSURE lockout on a YCAV?

Cycle the respective system switch OFF and ON — the manual requires this manual reset to clear a lockout. A plain FAULT needs no action: the system restarts once the pressure falls to 259 PSIG and the 120-second anti-recycle timer times out.

At what pressure does the YCAV trip on high discharge pressure?

The software cutout trips when the discharge pressure rises above 274 PSIG for 0.5 seconds. The system can restart when the pressure falls to 259 PSIG and is blocked from starting while the pressure is above that value.

Why does the system lock out instead of restarting?

After any 3 faults on the same system within 90 minutes, the system locks out on the last fault. From then on it stays off until you reset it by cycling the system switch OFF and ON.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YCAV; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: