Safety shutdown · YORK YCAV · Variable speed drive screw chiller

YORK YCAVSYS X HIGH MOTOR CURRENT

On the display

The panel shows SYS X HIGH MOTOR CURRENT. In the manual's fault tables the message is printed as SYS X YYYYYYY HIGH MOTOR CURRENT: X is the system number, and the YYYYYYY field reads FAULT for a condition that restarts or LOCKOUT once the system has locked out. The manual lists it among the VSD safeties (faults) and treats it as an individual system/compressor fault on all units.

What it means

This is a hardware-generated VSD fault, not a soft control alarm. Three current transformers inside the VSD monitor the three output lines to each phase of the compressor motor, and the instantaneous output current is compared against a predetermined hardware limit. If the peak current limit is exceeded, the unit faults and shuts down immediately. Because it is an individual system/compressor fault, it concerns the compressor of the system whose number appears in place of X on the display.

Why it appears

  • The instantaneous peak motor current on one or more phases exceeded the predetermined hardware limit that the VSD monitors through its three current transformers.
  • The manual names no other cause. It notes only that the trip point varies between units as a result of component tolerances on the VSD Logic Board, which is why the trip level is given as a nominal value with a minimum and a maximum.

Setpoints and thresholds

  • Nominal peak current trip level: 575.5 Amps (554A min., 597A max.).
  • On 380V AC 60 Hz and 400V AC 50 Hz units, the nominal peak current trip level is 649.5 Amps (626 Amps min., 674 Amps max.).
  • The trip level is a predetermined hardware limit in the VSD; the spread between the minimum and maximum figures comes from component tolerances on the VSD Logic Board.

Reset and restart

This is an auto-restart safety. After a trip the system restarts on its own, and the display shows the FAULT state. If the fault occurs a 3rd time within 90 minutes, the system locks out. A lockout will not restart until the operator clears the fault using the keypad. The manual describes no other reset for this fault.

Questions engineers ask

What does HIGH MOTOR CURRENT mean on a YORK YCAV?

It is a hardware-generated VSD fault: three current transformers in the VSD monitor the three output lines to each phase of the compressor motor, and the instantaneous current has exceeded a predetermined hardware peak limit, so the system shuts down immediately.

At how many amps does the YCAV trip on high motor current?

The nominal peak current trip level is 575.5 Amps (554A min., 597A max.). On 380V AC 60 Hz and 400V AC 50 Hz units it is 649.5 Amps (626 Amps min., 674 Amps max.), with the spread due to component tolerances on the VSD Logic Board.

How do I clear a HIGH MOTOR CURRENT lockout on a YCAV?

The fault is an auto-restart safety, but the system locks out on the 3rd fault in 90 minutes. A lockout will not restart until the operator clears the fault using the keypad.

Source

Written from the manufacturer's manuals for the YORK YCAV; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: