Safety shutdown · YORK YCAV · Variable speed drive screw chiller

YORK YCAVSYS X LOW DISCHARGE SUPERHEAT

On the display

The panel shows SYS X YYYYYYYY LOW DISCHARGE SUPERHEAT, where X stands for the number of the affected system. YYYYYYY indicates a "FAULT" condition or "LOCKOUT", so the status field tells you whether the safety has simply tripped or has escalated to a lockout. The same message is also listed without the status field, as SYS X LOW DISCHARGE SUPERHEAT.

What it means

This is the Low Discharge Superheat Cutout Fault, a system safety that produces a controlled ramped shutdown rather than an immediate stop. It helps protect the compressor primarily from liquid floodback through the economizer line due to a high flash tank level, and from liquid floodback through the suction line in conjunction with the low superheat safety. The safety is ignored for the first 5 minutes of compressor operation, so it can only trip once the compressor has run beyond that point.

Why it appears

  • After the first 5 minutes of compressor run time, the discharge superheat falls below 10.0°F and remains there for 5 minutes — this is the trip condition the manual gives for this safety.
  • The low discharge superheat reading points to liquid floodback into the compressor: primarily through the economizer line when the flash tank level is high, and through the suction line in conjunction with the low superheat safety.

Setpoints and thresholds

  • Trip threshold: discharge superheat below 10.0°F, sustained for 5 minutes.
  • Ignore window: the safety is ignored for the first 5 minutes of compressor operation.
  • Anti-recycle timer: 120 seconds before an automatic restart.
  • Lockout rule: 3 faults on the same system within 90 minutes.

Reset and restart

After a FAULT, the system restarts automatically when the 120-second anti-recycle timer times out. Once 3 faults have occurred on the same system within 90 minutes, the message shows LOCKOUT and the system will not restart until the operator clears the fault using the keypad; the manual states the lockout is cleared by cycling the system switch OFF and ON.

Questions engineers ask

What does SYS X LOW DISCHARGE SUPERHEAT mean on a YORK YCAV?

It is the Low Discharge Superheat Cutout Fault, a system safety that produces a controlled ramped shutdown. It protects the compressor from liquid floodback — primarily through the economizer line due to a high flash tank level, and through the suction line in conjunction with the low superheat safety.

What triggers the LOW DISCHARGE SUPERHEAT fault on a YCAV?

After the first 5 minutes of compressor run time, the fault trips when the discharge superheat falls below 10.0°F and stays there for 5 minutes. During the first 5 minutes of operation the safety is ignored.

Will the chiller restart by itself after a LOW DISCHARGE SUPERHEAT fault?

Yes — in a FAULT condition the system restarts when the 120-second anti-recycle timer times out. Only a LOCKOUT requires operator action.

How do I clear a LOW DISCHARGE SUPERHEAT LOCKOUT on a YCAV?

A LOCKOUT appears after 3 faults on the same system within 90 minutes, and the system will not restart until the operator clears the fault using the keypad. The lockout is cleared by cycling the system switch OFF and ON.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YCAV; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: