What it means
F33123 reports that the unipolar signal level of the A/B tracks of Encoder 3 has left the permissible window. The nominal unipolar level of the encoder must lie at 2500 mV +/- 500 mV; the drive responds when a level falls below 1700 mV or rises above 3300 mV. The level is only evaluated when the Sensor Module properties are available (r0459) and monitoring is active (p0437); outside these conditions the drive does not monitor the signal level at all. Depending on the drive configuration, the same condition can also be issued as an alarm (A) or with no reaction (N) instead of this fault.
Why it appears
- The unipolar level of one of the two signal pairs of Encoder 3 — AP/AN or BP/BN — is outside the permissible tolerance around the nominal signal level.
What to check
- Make sure that the encoder cables and the shielding are installed in an EMC-compliant manner.
- Check the plug connections and the contacts of the encoder cable.
- Check for a short-circuit of a signal cable with mass or with the operating voltage.
- Replace the encoder cable.
Reading the message value
The drive enters the fault cause into r0949 as a binary value ("Fault cause: %1 bin"). Interpret the value bit by bit:
- Bit 0 = 1: either AP or AN is outside the tolerance.
- Bit 16 = 1: either BP or BN is outside the tolerance.
Parameters the manual names
- r0949 — read the fault value here and interpret it in binary; bit 0 points to the AP/AN pair, bit 16 to the BP/BN pair.
- r0459 — check here that the Sensor Module properties are available; only then does the drive evaluate the signal level of Encoder 3.
- p0437 — check here that monitoring is active; without it the signal level of Encoder 3 is not evaluated.
Acknowledging and restarting
The fault must be acknowledged immediately. Once the signal level is back inside the permissible range and the fault has been acknowledged, the drive can be started again.
What differs between the drive families
Straight from the manuals' own fields — F33123 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Hla: OFF1 (NONE, OFF2, OFF3) | IMMEDIATELY | Actual position/speed value incorrect or not available (11) | Encoder 3 | SINAMICS S120, S150 List Manual · p. 3141 |
| G130, G150 | OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) | IMMEDIATELY | Actual position/speed value incorrect or not available (11) | Encoder 3 | SINAMICS G130, G150 List Manual · p. 1815 |
The drives this code lives on
F33123 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F33123 mean on a SINAMICS drive?
The unipolar signal level of Encoder 3 is outside the tolerance: the nominal level is 2500 mV +/- 500 mV, and the drive responds below 1700 mV or above 3300 mV.
How can I see whether the A or the B pair caused F33123?
Read the fault value in r0949 as a binary number: bit 0 = 1 means AP or AN is outside the tolerance, bit 16 = 1 means BP or BN is outside the tolerance.
How is fault F33123 acknowledged?
Correct the signal level problem first, then acknowledge the fault immediately; after the acknowledgement the drive can be started again.
Can F33123 also appear as an alarm?
Yes. Depending on the drive configuration, the same condition can also be output as an alarm (A) or with no reaction (N) instead of a fault.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F33xxx group · SINAMICS manuals · Siemens manuals