Fault · SINAMICS G130, G150, S120, S150

F33118Encoder 3: Speed change not plausible

What it means

F33118 is an Encoder 3 monitoring fault: for an HTL/TTL encoder, the drive has established that the speed change exceeds the tolerance in p0492 over several sampling cycles. The S120/S150 manual titles the message Encoder 3: Speed change not plausible, while the G130/G150 manual titles it Encoder 3: Speed difference outside the tolerance range; both describe the same condition. Where an averaged speed actual value is used, the drive additionally monitors the change of this averaged value within the current controller sampling time. Depending on the drive configuration, the same condition can also be issued as an alarm (A) or with no reaction (N).

Why it appears

  • For an HTL/TTL encoder, the speed change of Encoder 3 has exceeded the value in p0492 over several sampling cycles.
  • Where an averaged speed actual value exists, the drive also monitors the change of this averaged value in the current controller sampling time.

What to check

  1. Check the tachometer feeder cable for interruptions.
  2. Check the grounding of the tachometer shielding.
  3. If required, increase the maximum speed difference per sampling cycle in p0492.

Reading the message value

  • The drive stores the fault value in r0949, to be interpreted as a decimal number. Per the manual, this value is only for internal Siemens troubleshooting; no decoding is published.

Parameters the manual names

  • p0492 — square-wave encoder max. velocity difference per sampling cycle: the tolerance whose exceedance raises F33118 on Encoder 3; the remedy is to increase it if required.
  • r0949 — fault value: where the drive places the fault value of F33118, to be interpreted as a decimal number.

Acknowledging and restarting

The fault is acknowledged with pulse inhibit; once the cause has been remedied and the fault acknowledged, the drive can be restarted. When the drive is configured to issue the same condition as an alarm or with no reaction, neither a reaction nor an acknowledgement applies.

What differs between the drive families

Straight from the manuals' own fields — F33118 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Hla: OFF1 (NONE, OFF2, OFF3)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS S120, S150 List Manual · p. 3139
G130, G150OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS G130, G150 List Manual · p. 1813

The drives this code lives on

F33118 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F33118 in SINAMICS mean?

It reports that the speed of Encoder 3, an HTL/TTL encoder, has exceeded the tolerance in p0492 over several sampling cycles. The S120/S150 manual calls this 'Speed change not plausible', the G130/G150 manual 'Speed difference outside the tolerance range'.

How do I fix F33118?

Check the tachometer feeder cable for interruptions and check the grounding of the tachometer shielding; if required, increase the maximum speed difference per sampling cycle in p0492. Then acknowledge the fault with pulse inhibit.

Where can I read the fault value of F33118?

In r0949, interpreted as a decimal number. The manual states this value is only for internal Siemens troubleshooting and publishes no decoding.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.