Fault · SINAMICS G130, G150, S120, S150

F33126Encoder 3: Amplitude AB too high

What it means

F33126 reports that the signal level of Encoder 3 is above the permissible limit. The drive monitors the two incremental tracks A and B and responds when the sum of their magnitudes (|A| + |B|) exceeds 1120 mV, or when the amplitude — the root of A^2 + B^2 — exceeds 955 mV. For a healthy encoder, the nominal signal level lies between 375 mV and 600 mV (500 mV -25/+20 %).

The G130/G150 manual titles the code «Encoder 3: Amplitude AB too high», the S120/S150 manual «Encoder 3: Signal level track A or B too high»; both describe the same condition on the same component, so the page treats them together. Depending on how the drive is configured, the identical event can also be output only as an alarm or entirely without reaction.

Why it appears

  • The signal level of the encoder — the sum of the magnitudes of track A and track B (|A| + |B|) — exceeds the permissible limit value; the G130/G150 manual words the same cause as the amplitude (root of A^2 + B^2 or |A| + |B|) for Encoder 3 exceeding the permissible tolerance.

What to check

  1. Check that the encoder cables and the shielding are routed in compliance with EMC.
  2. Replace the encoder or the encoder cable.

Reading the message value

The message value contains the amplitude and the angle. The drive stores them in the fault value r0949; interpret the value hexadecimal as yyyyxxxx:

  • yyyy = Angle
  • xxxx = amplitude, i.e. the root of A^2 + B^2 (16 bits without sign)
  • Nominal signal level of the encoder: 375 mV to 600 mV (500 mV -25/+20 %)
  • The response threshold is reached when (|A| + |B|) exceeds 1120 mV or the root of (A^2 + B^2) exceeds 955 mV
  • A signal level of 500 mV peak value corresponds to the numerical value 10650
  • The angle 0 ... FFFF hex corresponds to 0 ... 360 degrees of the fine position; zero degrees is present at the negative zero crossover of track B
  • The amplitude and angle are not captured at the same instant as the hardware fault output: The analog values of the amplitude error are not measured at the same time with the hardware fault output by the Sensor Module.

Parameters the manual names

  • r0949 — fault value: for this code read it as a hexadecimal yyyyxxxx number, where the lower four digits xxxx give the measured amplitude (root of A^2 + B^2, 16 bits without sign) and the upper four digits yyyy the angle.

Acknowledging and restarting

Acknowledge the fault in PULSE INHIBIT mode: the pulse inhibit must be active before the drive accepts the acknowledgment. In practice the sequence is: let the drive's stop response bring the motor to a standstill, clear the condition on the encoder, acknowledge the fault, then restart. When the same event is configured as an alarm or with no reaction, the drive takes no action and nothing has to be acknowledged.

What differs between the drive families

Straight from the manuals' own fields — F33126 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Hla: OFF1 (NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS S120, S150 List Manual · p. 3142
G130, G150OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS G130, G150 List Manual · p. 1816

The drives this code lives on

F33126 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F33126 mean on a SINAMICS converter?

It reports that the signal level of Encoder 3 on tracks A and B is too high: the sum (|A| + |B|) exceeds 1120 mV or the amplitude (root of A^2 + B^2) exceeds 955 mV, while 375 mV to 600 mV is the nominal range.

How do I fix F33126?

Check that the encoder cables and their shielding are routed in compliance with EMC, and replace the encoder or the encoder cable if the event reappears.

How is F33126 acknowledged?

In PULSE INHIBIT mode: the pulses must be inhibited before the acknowledgment is accepted, after which the drive can restart. If the event is configured as an alarm or with no reaction, no acknowledgment is required.

What does the fault value of F33126 in r0949 contain?

A hexadecimal yyyyxxxx value: the upper four digits yyyy are the angle, the lower four digits xxxx the amplitude (root of A^2 + B^2, 16 bits without sign). A 500 mV peak signal level corresponds to the numerical value 10650.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.