Fault · SINAMICS G130, G150, S120, S150

F33130Encoder 3: Zero mark and position error from the coarse synchronization

What it means

F33130 means that after the pole position of Encoder 3 was initialized, the zero mark was detected outside the permissible range, and fine synchronization was therefore not carried out. The pole position may have been initialized using track C/D, Hall signals or the pole position identification routine. For distance-coded encoders, the test is carried out only after 2 zero marks have been passed. Depending on the configuration of the drive, the same condition can also be output as an alarm or without any reaction.

Why it appears

  • After initializing the pole position using track C/D, Hall signals or the pole position identification routine, the zero mark was detected outside the permissible range.
  • When initializing via track C/D (p0404), the drive checks whether the zero mark occurs within an angular range of +/-18 ° mechanical.
  • When initializing via Hall sensors (p0404) or pole position identification (p1982), the drive checks whether the zero mark occurs within an angular range of +/-60 ° electrical.

What to check

  1. Check that the encoder cables are routed in compliance with EMC.
  2. Check the plug connections.
  3. If the Hall sensor is used as an equivalent for track C/D, check the connection.
  4. Check the connection of track C or D.
  5. Replace the encoder or the encoder cable.

Reading the message value

In the message value, the drive reports the electrical angular deviation in %1 and the mechanical angle in %2. The fault value stored in r0949 is to be interpreted hexadecimal as yyyyxxxx:

  • yyyy — determined mechanical zero mark position (can only be used for track C/D).
  • xxxx — deviation of the zero mark from the expected position as electrical angle; scaling: 32768 dec = 180 °.

Parameters the manual names

  • r0949 — fault value of this message; read it hexadecimal as yyyyxxxx to see the determined mechanical zero mark position and the deviation as electrical angle (32768 dec = 180 °).
  • p0404 — effective encoder configuration; it shows whether the zero mark is judged against the +/-18 ° mechanical window (track C/D) or the +/-60 ° electrical window (Hall sensors).
  • p1982 — pole position identification selection; when initialization runs via this routine, the +/-60 ° electrical window applies.

Acknowledging and restarting

Once the cause has been eliminated, the fault is acknowledged; acknowledgement becomes possible when the pulse inhibit is present, after which the drive can be restarted.

What differs between the drive families

Straight from the manuals' own fields — F33130 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Hla: OFF1 (NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS S120, S150 List Manual · p. 3143
G130, G150OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS G130, G150 List Manual · p. 1817

The drives this code lives on

F33130 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F33130 in SINAMICS mean?

The zero mark of Encoder 3 was detected outside the permissible range after the pole position was initialized via track C/D, Hall signals or the pole position identification routine, so fine synchronization was not carried out.

Which zero mark tolerances apply to F33130?

With initialization via track C/D (p0404) the zero mark must occur within +/-18 ° mechanical; with Hall sensors (p0404) or pole position identification (p1982) within +/-60 ° electrical.

How is the fault value of F33130 decoded?

Read r0949 hexadecimal as yyyyxxxx: yyyy is the determined mechanical zero mark position (usable only for track C/D), and xxxx is the deviation from the expected position as electrical angle, scaled 32768 dec = 180 °.

How do I fix F33130?

Check EMC-compliant routing of the encoder cables, the plug connections, the Hall sensor connection when it serves as track C/D equivalent, and track C or D itself; if the fault persists, replace the encoder or encoder cable.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.