Fault · SINAMICS G130, G150, S120, S150

F33101Encoder 3: Zero mark failed

What it means

F33101 means that the zero mark monitoring on Encoder 3 has tripped: since POWER ON or since the last zero mark that was detected, the encoder has traveled 1.5 × the zero mark distance parameterized for this monitoring without a zero mark being recognized. The monitoring distance is taken from p0425 for a rotary encoder and from p0424 for a linear encoder. Depending on the drive configuration, the same condition can also be issued as an alarm (A) or without any reaction (N).

Why it appears

  • The distance traveled since POWER ON or since the last detected zero mark has exceeded 1.5 × the zero mark distance set in p0425 (rotary encoder) or p0424 (linear encoder).

What to check

  1. Check that the encoder cables are routed in compliance with EMC.
  2. Check the plug connections.
  3. Check the encoder type — the monitoring expects an encoder with equidistant zero marks.
  4. Adapt the parameterized clearance between zero marks (p0425) to the encoder actually connected.
  5. If the message is output above the speed threshold, reduce the filter time (p0438) if necessary.
  6. When bit 1 in p0437 is active, check p4686.
  7. If the fault remains, replace the encoder or the encoder cable.

Reading the message value

  • The message value (%1) is the fault value, which can be read in r0949 and is interpreted as a decimal number.
  • It contains the number of increments after POWER ON or since the last zero mark that was detected.
  • 4 increments correspond to 1 encoder pulse.

Parameters the manual names

  • p0425 — zero mark distance of a rotary encoder; adapt it when the parameterized clearance between zero marks does not match the encoder actually connected.
  • p0424 — zero mark distance of a linear encoder; on a linear measuring system the monitoring uses this distance.
  • r0949 — shows the fault value of F33101 as a decimal number: the increments since POWER ON or since the last detected zero mark.
  • p0438 — square-wave encoder filter time; reduce it if F33101 is only output above the speed threshold.
  • p0437 — extended Sensor Module configuration; when bit 1 of this parameter is set, check p4686.
  • p4686 — zero mark minimum length; check this value when bit 1 in p0437 is active.

Acknowledging and restarting

Acknowledgment is possible with the pulses inhibited: stop the drive so that pulse inhibit is reached, acknowledge the fault there and then restart the drive. When the drive is configured to issue the condition as an alarm (A) or without reaction (N), the manual specifies neither a reaction nor an acknowledgment.

What differs between the drive families

Straight from the manuals' own fields — F33101 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Hla: OFF1 (NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS S120, S150 List Manual · p. 3133
G130, G150OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 3SINAMICS G130, G150 List Manual · p. 1808

The drives this code lives on

F33101 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F33101 in SINAMICS mean?

The zero mark monitoring of Encoder 3 has tripped: more than 1.5 × the parameterized zero mark distance was traveled without a zero mark being detected. The distance comes from p0425 (rotary encoder) or p0424 (linear encoder).

What does the fault value of F33101 show?

In r0949, interpreted as a decimal number, the drive stores the number of increments after POWER ON or since the last zero mark that was detected. 4 increments correspond to 1 encoder pulse.

Which encoder do I need so that F33101 does not occur?

The monitoring expects an encoder with equidistant zero marks. Check the encoder type and adapt the clearance between zero marks in p0425 if it does not match the encoder actually connected.

How is F33101 acknowledged and cleared?

Bring the drive into pulse inhibit, acknowledge the fault there and restart. Depending on the configuration the condition can also appear as an alarm (A) or without reaction (N), in which case no acknowledgment is required.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.