What it means
F30625 means that the drive-integrated Safety Integrated function in monitoring channel 2 has detected an error in the sign-of-life of the safety data exchanged between the two monitoring channels and has therefore initiated a STOP A. On a G120 the manual words the same condition as a communication error between processor 1 and processor 2. The drive is stopped safely and will only restart once the fault has been acknowledged with a POWER ON (switch-off/switch-on).
Why it appears
- A DRIVE-CLiQ communication error between the two monitoring channels, or a failure of that communication (G130, G150, S120, S150). On a G120 the corresponding cause is a communication error between processor 1 and processor 2, or a failure of that communication.
- A time slice overflow of the safety software has occurred (all families).
- On G130, G150, S120 and S150 only: the enable of the safety functions in the two monitoring channels is inconsistent — p9601 = 0 while p9801 <> 0.
What to check
- Select Safe Torque Off and then de-select it again.
- Carry out a POWER ON (switch-off/switch-on); on the G130, G150, S120 and S150 the manual says to do this for all components.
- Check whether there is a DRIVE-CLiQ communication error between the two monitoring channels and, for any faults identified, carry out the diagnostics routine (G130, G150, S120, S150). On a G120, check instead whether additional faults are present and perform diagnostics as required.
- De-select all drive functions that are not absolutely necessary and reduce the number of drives (G130, G150, S120, S150 only).
- Check the electrical cabinet design and the cable routing for EMC compliance.
- On G130, G150, S120 and S150: check the enable of the safety functions for both monitoring channels (p9601, p9801) and correct it if required.
Reading the message value
The drive stores the fault value in r0949; interpret it as a decimal number. The manuals state that this value is only for internal Siemens troubleshooting and print no decoding of their own for it.
Parameters the manual names
- r0949 — displays the fault value of F30625; read it as a decimal. Its content is only meaningful for internal Siemens troubleshooting.
- p9601 — the enable of the Safety Integrated functions integrated in the drive on the Control Unit side; with this fault, check whether it is set inconsistently against p9801 (the manual names the combination p9601 = 0, p9801 <> 0) and correct it if required.
- p9801 — the enable of the Safety Integrated functions integrated in the drive on the Motor Module side; check it together with p9601 so that the safety functions are enabled consistently in both monitoring channels.
Acknowledging and restarting
Acknowledgement is by POWER ON: the drive is switched off and switched on again — on the G130, G150, S120 and S150 for all components. The remedy sequence first selects and de-selects Safe Torque Off and then performs the POWER ON. If F30625 comes back after the restart, work through the checks above, in particular the DRIVE-CLiQ communication between the monitoring channels and the consistency of p9601 and p9801.
What differs between the drive families
Straight from the manuals' own fields — F30625 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | None | SINAMICS G130, G150 List Manual · p. 1678 |
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | None | SINAMICS S120, S150 List Manual · p. 2976 |
| G120 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | — | SINAMICS G120 · p. 921 |
The drives this code lives on
F30625 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F30625 mean on a SINAMICS drive?
It means the Safety Integrated function in monitoring channel 2 has detected an error in the sign-of-life of the safety data between the two monitoring channels and has initiated a STOP A. On a G120 the manual describes this as a communication error between processor 1 and processor 2.
How is F30625 reset?
Select and de-select Safe Torque Off and then carry out a POWER ON (switch-off/switch-on); on the G130, G150, S120 and S150 this covers all components. The drive restarts only after this power cycle.
What causes F30625?
A DRIVE-CLiQ communication error or a communication failure between the two monitoring channels (processor 1 to processor 2 on a G120), or a time slice overflow of the safety software. On the G130, G150, S120 and S150 an inconsistent enable of the safety functions — p9601 = 0 with p9801 <> 0 — is also named.
Which parameters belong to fault F30625?
r0949 shows the fault value, which the manuals reserve for internal Siemens troubleshooting. p9601 and p9801 set the enable of the Safety Integrated functions on the Control Unit and Motor Module and must match so both monitoring channels are enabled consistently.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F30xxx group · SINAMICS manuals · Siemens manuals