What it means
F30600 is reported by the drive-integrated "Safety Integrated" (SI) function when its second monitoring channel has detected a fault and initiated a STOP A. The manual defines this STOP A as STO via the safety switch-off signal path of monitoring channel 2
. Two situations lead to it: the forced checking procedure (test stop) of this safety switch-off signal path was unsuccessful, or the fault is the subsequent response to F30611 (defect in a monitoring channel). The drive responds with OFF2, so it coasts to a standstill and will not restart until the fault has been acknowledged. On the G120 the manual describes the same event on processor 2 in terms of suppressed or enabled pulses rather than an active or inactive STO, and on HLA drive objects it is described for the Hydraulic Module. Which condition the drive saw is stored as a decimal fault value in r0949, and that value decides the remedy.
Why it appears
- The forced checking procedure (test stop) of the safety switch-off signal path of monitoring channel 2 was unsuccessful.
- The fault is the subsequent response to fault F30611 (defect in a monitoring channel).
- The concrete condition behind the STOP A is recorded as a decimal fault value in r0949 — see the decoding below.
What to check
- Read the fault value in r0949 and interpret it as a decimal number; the decoding below shows which condition the drive detected.
- Select Safe Torque Off (STO) and deselect it again.
- Carry out a POWER ON (switch-off/switch-on) for all components.
- For fault value 1005 on a Power Module with "STO via terminals at the Power Module" (terminals STO_A/STO_B): set both DIP switches to "OFF", or enable the "STO via terminals at the Power Module" function (it is disabled while p9601.7 = p9801.7 = 0).
- For fault value 1020: upgrade the Motor Module/Hydraulic Module software and, if required, replace the Motor Module/Hydraulic Module.
- For fault value 1030: check the discrepancy time and, if required, increase the value (p9650/p9850); then check the STO terminal at the Power Module (contact problems).
- For fault value 9999: carry out diagnostics for fault F30611.
- If the POWER ON does not clear the fault, replace the module involved — the Motor Module, the Power Module or the Motor Module/Hydraulic Module, depending on the converter.
Reading the message value
The drive stores the fault value in r0949; interpret it as a decimal number.
- 0 — stop request from the Control Unit; on a G120, from processor 1.
- 1005 — STO active although STO is not selected and no internal STOP A is present; on the G120, pulses suppressed although STO is not selected and no internal STOP A is present. On a Power Module with "STO via terminals at the Power Module" (STO_A/STO_B), the terminals are active (DIP switch to "ON") although the function is not enabled (p9601.7 = p9801.7 = 0).
- 1010 — STO inactive although STO is selected or an internal STOP A is present; on the G120, pulses enabled although STO is selected or an internal STOP A is present.
- 1011 — internal error for STO deselected in monitoring channel 2; on the G120, an internal fault for the pulse enable in the Power Module.
- 1020 (Motor Module/Hydraulic Module) — internal software error in the "Internal voltage protection" function. The function is withdrawn and
A STOP A that cannot be acknowledged is initiated.
- 1030 (Power Module, G120) — the feedback signals of the safety switch-off signal paths for the "STO via terminals at the Power Module" function are different.
- 9999 — subsequent response to fault F30611.
Parameters the manual names
- r0949 — fault value: read it here and interpret it as a decimal number to identify the condition that initiated the STOP A and pick the matching remedy.
- p9601 — SI enable functions integrated in the drive (Control Unit): its bit 7 enables the "STO via terminals at the Power Module" function whose absence is reported with fault value 1005.
- p9801 — SI enable functions integrated in the drive (Motor Module): the counterpart of p9601; with fault value 1005 both p9601.7 and p9801.7 are 0, i.e. the function is not enabled.
- p9650 — SI F-DI changeover discrepancy time (processor 1): for fault value 1030, check this discrepancy time and increase it if required.
- p9850 — SI F-DI changeover discrepancy time (processor 2): checked and increased together with p9650 for fault value 1030.
Acknowledging and restarting
The fault is acknowledged with a POWER ON, i.e. switching off and switching on again for all components; the manual's remedy additionally calls for selecting Safe Torque Off once and deselecting it again. If the fault comes back, work through the remedy for the specific fault value in r0949, and replace the Motor Module, Power Module or Hydraulic Module involved where the POWER ON does not help. Fault value 1020 is an exception: the STOP A initiated there cannot be acknowledged at all, so the Motor Module/Hydraulic Module software must be upgraded and the module replaced. After fault value 9999 the underlying fault F30611 must be diagnosed first.
What differs between the drive families
Straight from the manuals' own fields — F30600 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | None | SINAMICS S120, S150 List Manual · p. 2970 |
| G120 | OFF2 | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | — | SINAMICS G120 · p. 919 |
| G130, G150 | OFF2 | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | None | SINAMICS G130, G150 List Manual · p. 1675 |
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Safety monitoring channel has identified an error (10) | None | SINAMICS S120, S150 List Manual · p. 2971 |
The drives this code lives on
F30600 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F30600 SI P2: STOP A initiated mean?
The drive-integrated Safety Integrated function in monitoring channel 2 (processor 2 on a G120) detected a fault and initiated a STOP A, i.e. STO via the safety switch-off signal path. Either the test stop of this signal path was unsuccessful, or the fault is a subsequent response to F30611.
How do I clear and acknowledge F30600?
Select Safe Torque Off and deselect it again, then carry out a POWER ON (switch-off/switch-on) for all components. If the fault returns, read the fault value in r0949 and follow the remedy for that value.
F30600 shows fault value 1005 — what is wrong?
STO is active although it was not selected and no internal STOP A is present. On a Power Module with STO_A/STO_B terminals this means the DIP switches are ON while the function is not enabled (p9601.7 = p9801.7 = 0) — set both DIP switches to OFF or enable the "STO via terminals at the Power Module" function.
Why does F30600 keep coming back with fault value 9999?
Fault value 9999 is only the subsequent response to fault F30611 (defect in a monitoring channel). Carry out the diagnostics for F30611; the STOP A is a consequence, not the root cause.