Fault · SINAMICS G130, G150, S120, S150

F07501Drive: Motor Data Set MDS not configured

What it means

F07501 means that a drive data set refers to a motor data set (MDS) that has not been configured. The manual states this for power units: the motor data set was not configured, meaning that a data set number was not entered into the associated drive data set. Parameter p0186 is where a drive data set is given the number of its motor data set, so the fault is telling you that this entry is missing. Which drive data set is affected is shown in the message value (Drive data set: %1) and is contained in the fault value that the drive stores in r0949.

Why it appears

  • Only for power units: the motor data set was not configured.
  • Not configured here means that a data set number was not entered into the associated drive data set — p0186 is the parameter in which the drive data set receives the number of its motor data set.

What to check

  1. Read the fault value in r0949 and interpret it decimal: the fault value includes the drive data set number of p0186, so it identifies the drive data set whose motor data set is missing.
  2. Enter the index of the motor data set associated with this drive data set into p0186.

Reading the message value

  • The drive stores the fault value in r0949; the manual says to interpret it decimal.
  • The fault value includes the drive data set number of p0186.
  • The message value is printed as Drive data set: %1, so %1 is the affected drive data set.

Parameters the manual names

  • r0949 (Fault value): read the fault value here and interpret it decimal to obtain the drive data set number concerned by F07501.
  • p0186 (Motor Data Sets (MDS) number): enter here the index of the motor data set that belongs to the affected drive data set — this is the remedy for the fault.

Acknowledging and restarting

The fault trips the drive with OFF2, so the motor coasts down. After the index of the motor data set has been entered into p0186, acknowledge the fault immediately; the drive can then be started again.

The same on every family

Every manual that describes F07501 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150OFF2IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1569
S120, S150OFF2IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2833

The drives this code lives on

F07501 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F07501 mean?

The motor data set (MDS) was not configured: for a power unit, no data set number was entered into the associated drive data set, so the drive data set refers to a motor data set that has not been configured.

How do I fix fault F07501?

Enter the index of the motor data set associated with the affected drive data set into p0186, then acknowledge the fault immediately.

How can I see which drive data set triggers F07501?

Read the fault value in r0949 and interpret it decimal — the fault value includes the drive data set number of p0186. The message text also shows it as 'Drive data set: %1'.

Does F07501 stop the drive?

Yes, the drive coasts the motor down, and the fault must be acknowledged immediately before the drive will run again.