Fault · SINAMICS G130, G150, S120, S150

F07500Drive: Power unit data set PDS not configured

What it means

The drive raises F07500 — Drive: Power unit data set PDS not configured — when a drive data set is used for which no power unit data set (PDS) has been configured: a data set number was not entered into the drive data set. The fault concerns only controlled line supply infeed/regenerative feedback units. The message value names the affected drive data set, and the fault value in r0949, interpreted as a decimal number, contains the drive data set number of p0185.

Why it appears

  • The power unit data set was not configured — a data set number was not entered into the drive data set, so the drive data set in use references no power unit data set.
  • The condition is only monitored for controlled line supply infeed/regenerative feedback units; the manuals describe it identically for the controlled line supply infeed and regenerative feedback units of all listed converter families.

What to check

  1. Identify the affected drive data set: the message value shows the drive data set, and r0949 holds its number — read it there as a decimal value.
  2. Enter the index of the power unit data set associated with this drive data set into p0185.

Reading the message value

  • The message value shows the drive data set: the drive inserts the number of the affected drive data set for the placeholder %1.
  • Fault value (r0949, interpret decimal): drive data set number of p0185.

Parameters the manual names

  • r0949 (fault value): read it here as a decimal number to see which drive data set is affected — it contains the drive data set number of p0185.
  • p0185: enter here the index of the power unit data set that belongs to the affected drive data set; this entry is what the fault reports as missing.

Acknowledging and restarting

The drive does not trip on this fault. Once the index of the power unit data set belonging to the affected drive data set has been entered in p0185, acknowledge the fault immediately.

The same on every family

Every manual that describes F07500 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1569
S120, S150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2832

The drives this code lives on

F07500 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F07500 mean?

The drive data set in use has no power unit data set (PDS) configured — no data set number was entered into the drive data set. The fault is only raised for controlled line supply infeed/regenerative feedback units.

How do I fix fault F07500?

Enter the index of the power unit data set associated with the affected drive data set into p0185, and then acknowledge the fault immediately.

Which drive data set does F07500 refer to?

The message value shows the drive data set, and the fault value in r0949 — read as a decimal number — gives the drive data set number of p0185.

Does fault F07500 stop the drive?

No. The drive does not trip on this fault; it points to a missing entry in p0185 and is acknowledged immediately once the entry has been made.